BE1-CDS220
Time Overcurrent Characteristic Curves
A-1
APPENDIX A • TIME OVERCURRENT
CHARACTERISTIC CURVES
GENERAL
Basler Electric inverse time overcurrent systems (ANSI Device 51) provide time/current characteristic
curves that very closely emulate most of the common electro-mechanical, induction disk relays that were
manufactured in North America. To further improve proper relay coordination, selection of integrated reset
or instantaneous reset characteristics is also provided.
CURVE SPECIFICATIONS
Timing Accuracy (All 51 Functions):
Within ±5% or ±1½ cycles, whichever is greater,
for time dial settings of D greater than 0.1 and
multiples of 2 to 40 times the pickup setting but
not over 150 A for 5 A CT units or 30 A for 1 A CT
units.
Sixteen
inverse
time
functions,
one
fixed
time
function, and one programmable time function can
be selected. Characteristic curves for the inverse
and definite time functions are defined by the
following equations and comply with IEEE
C37.112 - 1996.
K
D
B
C
M
D
A
T
N
T
+
⋅
+
−
⋅
=
Equation A-1
1
M
D
R
T
2
R
−
⋅
=
Equation A-2
T
T
= Time to trip when M
≥
1
T
R
= Time to reset if relay is set for integrating
reset when M
<
1. Otherwise, reset is 50
milliseconds or less
D
= TIME DIAL setting (0.0 to 9.9)
M
= Multiple of PICKUP setting (0 to 40)
A, B, C, N, K
= Constants for the particular curve
R
= Constant defining the reset time.
Table A-1 lists time characteristic curve constants.
See Figures A-1 through A-16 for graphs of the
characteristics.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......