D-2 Settings
Calculations
BE1-CDS220
Step 1.
Determine the maximum CT secondary fault current for external faults at F (I
F3
for three-
phase, and I
FG
for single-phase). Refer to Figure D-1 for this example.
HIGH LOW
A
0
.
32
60
1916
I
F3
=
=
A
66
160
10603
I
F3
=
=
A
5
.
19
60
1171
I
FG
=
=
A
70
160
11231
I
FG
=
=
Step 2.
Determine the worst case CT burden voltage for a three-phase fault (V
B3
).
For
wye-connected
CTs:
)
R
R
(
I
V
R
L
F3
B3
+
=
For delta-connected CTs, for three-phase fault:
)
R
R
(
I
3
V
R
L
F3
B3
+
=
Note that the wye connection produces a lower burden on the CTs (see Setting Note 2).
Where:
Neglecting
R
R
, use R
L
from Table D-1.
HIGH LOW
V
4
.
22
)
7
.
0
)(
32
(
V
B3
=
=
V
2
.
46
)
7
.
0
)(
66
(
V
B3
=
=
Step 3.
Determine the worst case burden voltage for a line-to-ground fault (V
BG
).
For wye-connected CTs:
)
R
R
2
(
I
V
R
L
FG
BG
+
=
Where:
NOTE
This procedure uses the ANSI accuracy class method. See Setting Note 1 for
more information.
I
F3
= determined in Step 1
R
L
= one-way lead resistance in ohms
R
R
= relay resistance in ohms (< 0.05
Ω
)
I
FG
= determined in Step 1
R
L
= one-way lead resistance in ohms
R
R
= relay resistance in ohms
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......