13-70
Testing And Maintenance
BE1-CDS220
Command Purpose
SN-143=GROUP_MAN_SELECT,
GROUP1,NORMAL
Set Switch Names
SN-243=GROUP_MAN_SELECT,
GROUP2,NORMAL
Set Switch Names
SN-343=GROUP_MAN_SELECT,
GROUP3,NORMAL
Set Switch Names
SN-443=GROUP_CONTROL,
AUTO,MANUAL
Set Switch Names
SP-GROUP1=1,75,1,70,51P SG1
t
s
=1min@75%, t
r
=1min@70% of SG0 51P
SP-GROUP2=1,90,1,85,51P SG2
t
s
=1min@90%, t
r
=1min@85% of SG0 51P
SP-GROUP3=1,110,1,100,51P SG3
t
s
=1min@110%, t
r
=1min@100% of SG0 51P
E Exit
Y Save
settings
Step 3.
Switch group control to automatic using virtual switch 443. Use Table 13-81 ASCII commands
or front panel interface \CTRL\43\543, screen 2.1.6.
Table 13-81. Automatic Group Control Selection
Command Purpose
A= Gain
access
CS-443=1
Selects 443 for TRUE operation
CO-443=1
Executes 443 TRUE operation (AUTO)
Step 4.
Gain access if access timed out from the previous step. Send to the relay the appropriate
setting commands from Table 13-82. If your relay is supplied with the HMI option, you may
also go to the front panel interface screen \PROT\SG0\51\51 and edit the 51P settings. After
you send the commands to your relay, EXIT’ and (save) ‘Y’) the changes.
An ohmmeter or continuity tester may be used to monitor the output contacts (OUT1, OUT2,
and OUT3) status.
Table 13-82. Time Overcurrent 51P Element Pickup Settings
Sensing Input Type
Command Comments
1 A
S0-51P=1.0,5.0,I2
pu=1.0, td=5, curve=I2
S1-51P=1.5,5.0,I2
pu=1.5, td=5, curve=I2
S2-51P=1.8,5.0,I2
pu=1.8, td=5, curve=I2
S3-51P=2.2,5.0,I2
pu=2.2, td=5, curve=I2
5 A
S0-51P=5.0,5.0,I2
pu=5.0, td=5, curve=I2
S1-51P=7.5,5.0,I2
pu=7.5, td=5, curve=I2
S2-51P=9.0,5.0,I2
pu=9.0, td=5, curve=I2
S3-51P=11.0,5.0,I2
pu=10.5, td=5, curve=I2
Step 5.
Using the values listed in Table 13-83, apply current to the A phase current input, beginning at
the starting point, then stepping up to just slightly above the threshold limit for the amount of
time listed. If the active setting group does not change, step the current up to just below the
next group switch limit for the duration indicated. The setting group change should occur
between the low and high limits. Monitor the output contacts to verify that the change occurred
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......