6-30
Reporting and Alarm Functions
BE1-CDS220
SG-TRIGGER Command
Purpose:
Read/Set Trigger logic
Syntax:
SG-TRIGGER[={TRIP trig},{PU trig},{LOGIC trig}]
Comments:
The BESTlogic rules for input logic apply to the definition of the <trigger logic> which only
allows OR and NOT operators in the Boolean logic equation.
SG-TRIGGER Command Example:
Example 1.
Make the following BESTlogic settings to the Fault Recording function. See Figure 6-16.
Tripped: VO9
Picked up:
VO10+VO11
Logic:
/IN2
Targets
Each protective function (see Table 6-15) logs target information to the fault reporting function when a trip
condition occurs and the trip output of the function block becomes TRUE (refer to Figure 6-9 and Table 6-
11, call-out B). Target information can be viewed and reset at the HMI and through the communication
ports.
Table 6-15. Protective Functions with Targets
Name Protective
Function
Target
Default
87R
Phase Differential Restrained Pickup
Enabled
87U
Phase Differential Unrestrained Pickup
Enabled
87ND
Neutral Differential Restrained Pickup
Enabled
51P, 151P, 251P
Phase Inverse Time Overcurrent
Enabled
51N, 151N, 251N
Neutral Inverse Time Overcurrent
Enabled
51Q, 151Q, 251Q
Negative-Sequence Inverse Time Overcurrent
Enabled
50TP, 150TP, 250TP
Phase Instantaneous Overcurrent
Enabled
50TN, 150TN, 250TN
Neutral Instantaneous Overcurrent
Enabled
50TQ, 150TQ, 250TQ
Negative-Sequence Instantaneous Overcurrent
Enabled
BF Breaker
Failure
Enabled
62, 162
General Purpose Logic Timer
Enabled
Target logging for a protective function can be disabled if the function is used in a supervisory or
monitoring capacity. The following paragraphs describe how the relay is programmed to define which
protective functions log targets.
Setting the Targets Function
Targets are enabled using the BESTCOMS screen shown in Figure 6-17. You can select which protective
elements trigger a target and what type of logic condition will reset the targets. To open the screen, select
Reporting and Alarms from the Screens pull-down menu. Then select the Fault Recording tab. Enable the
targets by checking the appropriate boxes.
Alternately, targets can be enabled using the SG-TARG ASCII command. Using the SG-TARG command,
you can select which protective elements trigger a target and what type of logic condition will reset the
targets.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......