4-36 Protection
and
Control BE1-CDS220
Mode 5, Integrating Timer
An integrating timer is similar to a pickup/dropout timer except that the PICKUP time T1 defines the rate
that the timer integrates toward timing out and setting the output to TRUE. Conversely, the RESET time
T2 defines the rate that the timer integrates toward dropout and resetting the output to FALSE. PICKUP
time T1 defines the time delay for the output to change to TRUE if the initiate input becomes TRUE and
stays TRUE. RESET time T2 defines the time delay for the output to change to FALSE if it is presently
TRUE and the initiate input becomes FALSE and stays FALSE.
In the example shown in Figure 4-35, RESET time T2 is set to half of the PICKUP time T1 setting. The
initiate input expression becomes TRUE and the timer starts integrating toward pickup. Prior to timing out,
the initiate expression toggles to FALSE and the timer starts resetting at twice the rate as it was
integrating toward time out. It stays FALSE long enough for the integrating timer to reset completely but
then toggles back to TRUE and stays TRUE for the entire duration of time T1. At that point, the output of
the timer is toggled to TRUE. Then later, the initiate expression becomes FALSE and stays FALSE for the
duration of RESET time T2. At that point, the output of the timer is toggled to FALSE.
D2843-12
10-23-03
Figure 4-35. Mode 5, Integrating Timer
This type of timer is useful in applications where a monitored signal may be hovering at its threshold
between on and off. For example, it is desired to take some action when current is above a certain level
for a certain period. A 50T function could be used to monitor the current level. Thus, if the current level is
near the threshold so that the
INITIATE
input toggles between TRUE and FALSE from time to time, the
function will still time out as long as the time that it is TRUE is longer than the time that it is FALSE. With a
simple pickup/dropout timer, the timing function would reset to zero and start over each time the initiate
expression became FALSE.
Mode 6, Latch
A one shot timer starts its timing sequence when the
INITIATE
input expression changes from FALSE to
TRUE. The timer will time for DELAY time T1 and then the output will latch TRUE. Additional
INITIATE
input expression changes of state are ignored. Time (T2) is ignored. Refer to Figure 4-36.
D2863-07
10-23-03
Figure 4-36. Mode 6, Latch
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......