BE1-CDS220
Testing And Maintenance
13-49
circuit
monitor
current
source 1
180 degrees
current
source 2
B1 B3 B5 B7
B2 B4 B6 B8
B9 B11 B13 B15
B10 B12 B14 B16
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
Figure 13-16. Connection for 87ND Restraint Pickup Verification
Step 2.
To prepare the 87ND element for testing the restraint operation accuracy, transmit the
commands in Table 13-37 to the relay.
Table 13-37. 87ND Restraint Operation Accuracy Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm
overwrite
SL-N=NDIFF
Name custom logic for this test
SL-87=0 Disables
87
SL-87ND=2,0
Enables 87ND, mode=IG v. CT2, no blk
SL-VO1=87NDT
Enables OUT1 to close for 87ND restrained trip
SG-CT2=1,WYE,NA,0
input 2 ctr=1, ct=wye, xfmr=na, no grd source
SG-CTG=1
gnd input ctr=1
SG-TRIGGER=87NDT,
87NDPU,0
Enable 87NDT to log and trigger fault recording
S#-87ND=0.35,15,50m
Minpu = 0.35, slope = 15%, minimum time delay
E Exit
Y Save
settings
NOTE
The ground differential function always uses the maximum restraint principle as its
operating characteristic. Thus, the slope setting is simply a number between 15 and 60.
Step 3.
The auto tap compensation logic of the relay will calculate TAPN and TAPG values based on
CT ratios for the designated phase CTs and the ground CT. Since CTR2 and CTRG are both
equal to 1:1 for this test, the TAPN and TAPG values are both equal to the minimum settings
for either 5 ampere or 1 ampere relays (2.0 and 0.4 respectively).
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......