BE1-CDS220
Testing And Maintenance
13-7
NOTE
If your relay is not supplied with the front panel HMI option, skip Steps 7 through 10 and
proceed to the Current Circuit Verification test.
Step 7.
From the HMI keypad, navigate to the screen \CTRL\OUT (Output Control Override) to
override control of the outputs via the keypad.
Step 8.
Once you have accessed the screen, press the EDIT pushbutton. Select an output to override
by using the left/right arrow pushbuttons. Once selected, use the up/down arrow pushbuttons
to choose the type of action (P, 1, or 0) for the selected contact output. Select the pulse (P)
action for the alarm contact (A). Pressing the EDIT pushbutton again will force the alarm output
contact action.
Step 9.
Verify that the sequence of events recorder logged the events by sending the command RS-2
to the relay (requesting the last two events it logged). The close-open pulse action should be
listed as two separate events.
Step 10. Repeat Step 8 for all desired output contacts, and then verify that the sequence of events
recorder logged the events.
Current Circuit Verification
Purpose: To verify that the relay internal CT circuits accurately measures currents and polarities.
Reference Commands: M-I, SG-TARG, SG-TRIGGER, RS
Step 1.
Connect in series, one current
source to terminals B1, B2 (I
A1
),
B3, B4 (I
B1
), B5, B6 (I
C1
), B7, B8
(I
G
if present), B10, B9 (I
A2
), B12,
B11 (I
B2
), B14, B13 (I
C2
). See
Figure 13-2. Notice that CT
circuit 2 polarities are reversed.
Figure 13-2. Series Current Connection Diagram
Step 2.
Apply 5 amperes of current to 5 ampere rated CT inputs (or 1 ampere to 1 ampere rated CT
inputs).
Step 3.
Transmit the command M1-I to the relay, or navigate to the front panel HMI screen
\METER\CRNT\CT_1\I_MEAS (3.1.1.1) and \METER\CRNT\CT_1\I_CALC (3.1.1.2) and verify
the values listed in Table 13-4.
Table 13-4. Circuit 1 Metering Quantities
CT secondary
I
A1,
I
B1,
And I
C1
I
N1
I
Q1
5 A
5.0 A (
±
1%) @ 0
o
15.0 A (
±
1%) @ 0
°
0.0 A (
±
1%)
1 A
1.0 A (
±
1%) @ 0
o
3.0 A (
±
1%) @ 0
°
0.0 A (
±
1%)
Circuit
Monitor
Current
Source 1
180 Degrees
Current
Source 2
B1 B3 B5 B7
B2 B4 B6 B8
B9 B11 B13 B15
B10 B12 B14 B16
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
D2857-07.vsd
05-05-00
Typical Jumpers
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......