4-38 Protection
and
Control BE1-CDS220
Example 1.
Make the following settings to the 62 Logic Timer. Figure 4-37 illustrates these settings.
Logic:
User
Mode:
One Shot Non-Retriggerable
INITIATE:
IN2
BLOCK:
0
Operating Settings for General Purpose Logic Timers
Operating settings are made using BESTCOMS. Figure 4-38 illustrates the BESTCOMS screen used to
select operational settings for the Logic Timer elements. To open the
Logic Timers
screen, select
Logic
Timers
from the
Screens
pull-down menu. Alternately, settings may be made using the S<g>-x62 ASCII
command or through the optional HMI interface using Screen 5.#.5.1, \PROT\SG#\62\SETTINGS.
Figure 4-38. Logic Timers Screen
At the top left of the screen is a pull-down menu labeled
Logic
. This menu allows viewing of the
BESTlogic settings for each preprogrammed logic scheme. User or custom logic
must
be selected on this
menu in order to allow changes to be made to the mode and inputs of the element.
Beneath the
Logic
pull-down menu is a pull-down menu labeled
Settings
. The Settings menu is used to
select the setting group that the element's settings apply to. See Section 7,
BESTlogic Programmable
Logic, Logic Schemes
.
Using the pull-down menus and buttons, make the application appropriate settings to the Logic Timer
elements.
Table 4-20 summarizes the operating settings for General Purpose Logic Timers.
Table 4-20. Operating Settings for General Purpose Logic Timers
Setting
Range
Increment
Unit of Measure
Default
0 to 999 ms
1
Milliseconds
0.1 for 0.1 to 9.9 sec.
0.1 to 9999 sec.
1.0 for 10 to 9999 sec.
Seconds
T1 Time,
T2 Time
0 to 599,940 (60 Hz)
0 to 499,950 (50Hz)
∗
Cycles
0
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......