BE1-CDS220
Testing And Maintenance
13-45
Step 1.
Connect one current source to terminals B1, B2 (A-phase, input 1). Refer to Figure 13-1.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2.
Send the commands listed in Table 13-31 to the relay to setup a test of the pickup of the 87
elements.
Table 13-31. 87 Elements Pickup Setup Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm
overwrite
SL-N=UDIFF
Name custom logic for this test
SL-87=1,0 Enables
87
SL-VO1=87UT
Enables OUT1 to close with 87 unrestrained trip
SL-VO2=5THHAR
Enables OUT2 to close when 5
th
harmonic restrains
87RT
SG-CT1=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87UT,87UT,0
Enable 87UT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
S#-87=0,15,0,0,1,1
Minpu = disabled, slope = 15%, 2
nd
= disabled, 5
th
=
disabled, URO = disabled, 2
nd
harm sharing = shared
E Exit
Y Save
settings
Step 3.
Apply current to A-phase input 1, increasing the magnitude until OUT1 closes. Since the URO
setting is 1 and Tap 1= 2, this should occur at 2 amperes. Accuracy when increasing or
decreasing the input current is
±
4% of setting or 75 milliamperes (whichever is larger) for 5
ampere sensing inputs and
±
4% of setting or 25 milliamperes (whichever is larger) for 1
ampere sensing inputs. Verify that pickup occurred within the specified accuracy of the relay.
Step 4.
Reduce the input current until OUT1 opens.
Step 5.
Using the values in Table 13-32, repeat Step 3 for the other values of unrestrained settings
indicated.
Table 13-32. Unrestrained Pickup Accuracy Limits
URO Setting
Tap 1
Pickup (A)
Low Limit (A)
High Limit (A)
1 2.00 2 1.925 2.075
5 2.00
10 9.700 10.30
10 2.00 20 19.40 20.60
Step 6.
(Optional) Repeat steps 1 through 5 for phases B and C.
Step 7.
(Optional) Repeat Steps 2 through 6 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
Unrestrained Time Verification
A timing circuit or a contact monitor with timing algorithm must be used to time the output contact status
change. For more information on determining the minimum pickup current, refer to Sidebar 13-8.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......