13-50
Testing And Maintenance
BE1-CDS220
NOTE
Tables 13-38 and 13-39 show values for testing the relay either by increasing input 2
(neutral) current or decreasing the ground input current. Both methods are shown for
convenience and either method may be used. For differences in measurement of the two
methods, refer to the paragraphs in this Section,
Functional Testing
,
Restrained Pickup
and Sidebar 13-3,
Maximum Restraint Operating Characteristic
.
Step 4.
Input current values for this step are provided in Table 13-38 or 13-39. Apply balancing current
to phase A input 2 (represented as the Neutral column) and the ground input as indicated in
each row and slowly increase phase A input 2 until OUT1 closes.
Step 5.
Remove both currents.
Step 6.
Verify the restrained pickup accuracy as listed in the appropriate Table (13-38 or 13-39).
Step 7.
(Optional) Repeat Steps 2 through 6 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
Table 13-38. Restraint Pickup Test Points (87ND – 5 Ampere Sensing Input)
Sensing
Neutral (Input 2)
Ground
Increasing Input 2
Decreasing I
G
Input Minimum slope
Calc. Tap =
2.00
Calc. Tap =
2.00
From Balance
From Balance
Type
Pickup
(%)
Bal. Input (A)
PU
Bal. Input (A)
PU
Pickup (A)
Pickup (A)
5
0.35
15
2.00 1 2.00 1
2.70
±
0.108 1.30
±
0.075
5
0.35
15
10.00 5 10.00 5
11.76
±
0.470 8.50
±
0.340
5
0.35
30
2.00 1 2.00 1
2.86
±
0.108 1.30
±
0.075
5
0.35
30
10.00 5 10.00 5
14.29
±
0.572 7.00
±
0.280
5
0.35
45
2.00 1 2.00 1
3.64
±
0.146 1.10
±
0.075
5
0.35
45
10.00 5 10.00 5
18.18
±
0.727 5.50
±
0.220
5
0.35
60
2.00 1 2.00 1
5.00
±
0.200 0.80
±
0.075
5
0.35
60
10.00 5 10.00 5
25.00
±
0.100 4.00
±
0.160
Table 13-39. Restraint Pickup Test Points (87ND – 1 Ampere Sensing Input)
Sensing
Input 1
Input 2
Increasing Input 1
Decreasing Input 2
Input Minimum slope
tap =
2.00
tap =
3.80
From Balance
From Balance
Type
Pickup
(%)
Bal. Input (A)
PU
Bal. Input (A)
PU
Pickup (A)
Pickup (A)
1
0.35
15
0.40 1 0.40 1
0.54
±
0.025 0.26
±
0.025
1
0.35
15
2.00 5 2.00 5
2.35
±
0.094 1.70
±
0.068
1
0.35
30
0.40 1 0.40 1
0.57
±
0.025 0.26
±
0.025
1
0.35
30
2.00 5 2.00 5
2.86
±
0.114 1.40
±
0.056
1
0.35
45
0.40 1 0.40 1
0.73
±
0.029 0.22
±
0.025
1
0.35
45
2.00 5 2.00 5
3.64
±
0.146 1.10
±
0.044
1
0.35
60
0.40 1 0.40 1
1.00
±
0.040 0.16
±
0.025
1
0.35
60
2.00 5 2.00 5
5.00
±
0.200 0.80
±
0.032
Instantaneous Overcurrent
Pickup and Dropout Verification (50T/150T/250T)
Purpose:
To verify the accuracy of the operation of the 50T/150T/250T elements.
Reference Commands:
SL-50T/150T/250T, SL-GROUP, SL-VO
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......