BE1-CDS220
Testing And Maintenance
13-29
Step 2.
To prepare the 87 elements for testing, transmit the commands in Table 13-13 to the relay.
Table 13-13. Pickup Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm
overwrite
SL-N=RDIFF
Name custom logic for this test
SL-87=1,0 Enables
87
SL-VO1=87RT
Enables OUT1 to close for 87 restrained trip
SG-CT1=1,WYE,NA
ctr=1, ct=wye, xfmr=na
SG-CT2=1,WYE,NA
ctr=1, ct=wye, xfmr=na
SG-TRIGGER=87RT,
7RPU,0
Enable 87RT to log and trigger fault recording
E Exit
Y Save
settings
Step 3.
Send to the relay the commands listed in Table 13-14.
NOTE
The tap settings listed in the S#-TAP87 command are within the range of settings for a 5
ampere sensing input type relay. If your relay is a 1 ampere sensing input type, change
the TAP 1 and TAP 2 values to 1.0.
Table 13-14. S#-87 Commands
Command Purpose
A= Gain
access
S#-TAP87=MANUAL,
5.00,5.00
Set TAP 1=5.00 and TAP 2=5.00
S#-87=0.1,15,0,0,0,1
Minpu = 0.1, slope = 15%, 2
nd
= disable, 5
th
= dis-
able, URO = disable, 2
nd
harm sharing = 1 (yes)
E Exit
Y Save
settings
Step 4.
Apply current to phase A, input 1 and slowly ramp up until OUT1 closes. The relay should
pickup at a value of minimum pickup x TAP (see Figure 13-12).
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......