8-24 Application BE1-CDS220
Table 8-17. TX-W-BU Contact Input Logic
State Labels
Input
Purpose Name
Label
Closed Open
IN1
Optional input. Used for CT input circuit 1 breaker status
indication in SER reports. TRUE when breaker closed.
BREAKER-1
CLOSED
OPEN
IN2
Optional input. Used for CT input circuit 2 breaker status
indication in SER reports. TRUE when breaker closed.
BREAKER-2
CLOSED
OPEN
IN3
Optional input. Used for 86T status indication and locks out the
low-side breaker when TRUE. TRUE when 86T is tripped.
86T-TRIPPED
TRIPPED
NORMAL
IN4
Optional input. Used for 86B status indication and locks out the
low-side breaker when TRUE. TRUE when 86B is tripped.
86B-TRIPPED
TRIPPED
NORMAL
IN5
Puts transformer and bus relays in feeder backup mode when
feeder relay out-of-service is detected by an open contact.
Feeder relays such as BE1-851 or BE1-951 using one of the
preprogrammed schemes with interlock logic.
FEEDERS_OK
NORMAL FDR_OOS
IN6
Breaker Failure Initiate by external relays with breaker status
supervision. Typically used for differential or sudden pressure
tripping.
EXT-BFI-52B-
SUPV
INI
NORMAL
IN7
Breaker Failure Initiate by external relays with fault detector
supervision. Typically used for overcurrent tripping relays.
EXT-BFI-50-
SUPV
INI
NORMAL
IN8
Puts the relay in test mode so that breaker failure is disabled
when input 8 is de-energized.
TEST-MODE-
DISABL
NORMAL TSTMODE
Table 8-18. TX-W-BU Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode Setting
87
Used for percent-restrained differential protection with high-speed
unrestrained instantaneous differential protection. Differential function
is blocked when virtual switch 43 is TRUE.
43
1 (Enabled)
51N
Used for timed ground-overcurrent protection for independent ground
input circuit.
0
G (Ground Input)
151P
Used for timed phase-overcurrent protection for CT input circuit 1.
0
1 (CT Input 1)
151N
Used for timed neutral-overcurrent protection for CT input circuit 1.
0
1 (CT Input 1)
151Q
Used for timed negative sequence-overcurrent protection for CT input
circuit 1.
0
1 (CT Input 1)
NOTE
Tables 8-17 through 8-20 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches,
and outputs in use for the TX-W-BU preprogrammed logic are described in the
following Tables.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......