BE1-CDS220
Testing And Maintenance
13-47
Step 12.
(Optional) Repeat Steps 3 through 11 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
Neutral Differential (87ND)
Minimum Pickup
Purpose:
To verify the accuracy of the restraint operation of the 87ND element.
Reference Commands:
SL-87ND, SL- VO, SG-CT, S(n)-87, S(n)-TAP87
Step 1.
Connect current source 1 to terminals B7 and B8 (ground input). See Figure 13-15. An ohm-
meter or continuity tester may be used to monitor output contact status.
circuit
monitor
current
source 1
180 degrees
current
source 2
B1 B3 B5 B7
B2 B4 B6 B8
B9 B11 B13 B15
B10 B12 B14 B16
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
Figure 13-15. Connection for 87ND Minimum Pickup Verification
Step 2.
To prepare the 87ND element for testing, transmit the commands in Table 13-35 to the relay.
Table 13-35. 87ND Pickup Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm
overwrite
SL-N=NDIFF
Name custom logic for this test
SL-87=0 Disables
87
SL-87ND=2,0
Enables 87ND, mode=IG v. CT2, no blk
SL-VO1=87NDT
Enables OUT1 to close for 87ND restrained trip
SG-CT2=1,WYE,NA,0
input 2 ctr=1, ct=wye, xfmr=na, no grd source
SG-CTG=1
gnd input ctr=1
SG-TRIGGER=87NDT,
87NDPU,0
Enable 87NDT to log and trigger fault recording
S#-87ND=0.1,15,50m
Minpu = 0.1, slope = 15%, 50 ms (minimum time
delay)
E Exit
Y Save
settings
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......