BE1-CDS220 Settings
Calculations
D-5
Step 5:
Calculate actual tap settings. Choose the tap that is out of range, and adjust to the nearest
valid tap setting.
Step 6:
Calculate the opposite actual tap such that Equation D-5 is true.
2
1
2
1
ActualTap
ActualTap
IdealTap
IdealTap
=
Equation D-5
Calculate Minpu
The minimum pickup restraint setting (Minpu) adjusts the sensitivity of the relay. In non-numerical relays,
the Minpu was fixed at a typical value of 0.35 of the relay tap. In the BE1-CDS220 relay, the user can
choose lower or higher values to optimize the protection in each particular application. Selecting a lower
minpu setting will tend to raise the slope setting to maintain a given margin at the knee-point of the
differential tripping characteristic (for more information, see the Calculate Slope paragraphs later in this
section). Conversely, it is sometimes necessary to accommodate unmonitored loads in the differential
zone. In that case, the minpu setting may be higher. A setting of 0.25 per unit of transformer full load (FA)
rating is recommended for typical installations where no unmonitored load needs to be considered. This
value is well above the magnetizing current and provides a safe margin at the knee point of the slope
characteristic. If unmonitored loads such as station service or small capacitor banks are connected in the
differential zone, the minpu must be increased by the magnitude of the unmonitored current in multiples of
tap.
Step 1:
Calculate desired minimum pickup setting in times tap. Choose the desired minimum pickup
in per unit on the transformer full load base (0.25). Multiply times the factor X calculated using
Equation D-6. If the ideal tap (TAP
nI
) is equal to the actual tap (TAP
nA
), the factor will be 1.
For this example, this is the case, so the minimum pickup of 0.25 per unit will equal a
minimum pickup of 0.25 times tap.
CTRn
KVn
TAP
COMP
MVA
Tap
TAP
X
nA
n
nA
nI
∗
∗
∗
∗
∗
=
=
3
1000
Equation D-6
Step 2:
Calculate the unmonitored load in times tap. Use Equation D-7.
CTRn
TAP
COMPn
pri
Iunmon
Iunmon
n
∗
∗
=
0
=
Iunmon
Equation D-7
Step 3:
Calculate the Minpu setting. Add the two to get the Minpu setting.
Minpu = 0.25 + 0
= 0.25
NOTE
Unmonitored capacitor banks should be avoided if possible, or they must be
treated very carefully to avoid false tripping due to inrush currents.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......