BE1-CDS220 Installation
12-23
AØ
BØ
CØ
Circuit
Switcher
P0035-22
01-06-06
With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or delta AC). for more information, refer to Section 3, Input And Output
Functions, Input Current.
Optional independent groupd input (
I
G
) connected to detect low side ground faults.
Phase, Residual, and Negative-Sequence overcurrent elements can be connected to either CT circuit for
backup protectiion. For more information on applying overcurrent backup, refer to Section 8, Application.
(Residual current not available on delta connected CTs.)
Overcurrent neutral ground (
I
N
) operates on internally calculated residual (3I0) current.
For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
Element with the BE1-CDS220 (refer to Figure 12-18 for a connection diagram). To add only metering to
the BE1-CDS220, connect a BE1-MMS100.
1
2
3
1
BE1-CDS220
B2
B1
B3
B4
I
B1
I
A1
1
B10
B14
B12
B9
I
A2
I
B2
I
C2
B13
B11
3
2
X1
X2
X3
DAB
3
4
5
Bus or Line
Low Side Breaker
B5
B6
I
C1
B8
B7
I
G
4
H3
H2
H1
A
B
C
C-A
B-C
A-B
A
B
C
C-A
B-C
A-B
C
A
B
Figure 12-26. Differential Protection of DAB-Wye Grounded Transformer with Y-D CTs and Optional
Independent Ground Input Connected for Low Side Ground Fault Protection.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......