6-20
Reporting and Alarm Functions
BE1-CDS220
Figure 6-8. Reporting and Alarms Screen, Breaker Monitoring Tab
Table 6-10 lists the settings for the breaker status reporting function.
Table 6-10. Breaker Status Reporting Settings
Setting Range/Purpose
Default
Breaker Closed Logic
Logic expression that is TRUE when the breaker is
closed (e.g., 52a logic)
0
Breaker Label
16 character alpha/numerical label (name)
BREAKER_LABEL
SB-LOGIC Command
Purpose:
Read/Set Breaker Contact Logic
Syntax:
SB-LOGIC[={breaker close logic},{breaker name}]
Comments:
n =1, 2, 3, 4 for Ckt 1, Ckt 2, Ckt 3, Ckt 4.
SB-LOGIC Command Example:
Example 1.
Set the relay to monitor input 3 so that when the input is false, the breaker is closed (52b
contact is wired to Input 3) and change breaker label to BREAKER_1.
>SB-LOGIC
=
/IN3,BREAKER_1
Retrieving Breaker Status and Operation Counter Information
The current breaker status can be read from HMI Screen 1.4.5, \STAT\OPER\BKR and from the ASCII
command interface using the RG-STAT or RG-BREAKER command. The paragraphs on General Status
Reporting in this section provide more information on this command.
The current value of the breaker operations counter register can be read from HMI Screen 4.3.1,
\REPRT\BRPTS\STATUS. Pressing the Edit key allows the user to enter a number into the register to
NOTE
The NOT symbol (/) is applied to the variable immediately following the symbol.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......