13-4
Testing And Maintenance
BE1-CDS220
Figure 13-1. BE1-CDS, Rear View, Terminal Connections
Power Up
Purpose: To verify that the relay performs the power-up sequence.
Step 1. Apply voltage to input power terminals A2 and A3. Table 13-1 shows the appropriate voltage
for each relay style.
Table 13-1. Voltage Input
Style Number
Voltage Input
BE1-CDS2 2 0 - x x x x x x L x x x x x 24
Vdc
BE1-CDS2 2 0 - x x x x x x Y x x x x x 48/125 Vac/dc
BE1-CDS2 2 0 - x x x x x x Z x x x x x
125/250 Vac/dc
Step 2. Verify that the Power LED is ON, and that characters are displayed on the HMI display (if
option Y - 6 pushbutton HMI with LCD display is selected). Upon power-up, the relay will
perform a brief self test.
During this brief test, all front panel LEDs will flash momentarily, the display will indicate each
step of the self test, relay model, software version and then settle into the default display
screen. Contact Basler Electric, Customer Service if anything appears out of the ordinary or if
the LCD code error messages appear.
Communications
Purpose: To verify that the BE1-CDS relay communicates through all ports.
Reference Commands: ACCESS, EXIT
To communicate with the BE1-CDS220 through any of the three ports, you may use either a VT-100
terminal or a personal computer (PC) with a serial port and suitable communications software. The relay
communication default settings are:
•
Baud Rate = 9600 bps
•
Data Bits = 8
•
Stop Bit =1
•
Parity = None
•
Flow Control = Xon/Xoff.
Please see appendix D for more information on Terminal and HyperTerminal setups for Windows
3.1,
Windows
95, and Windows
98.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......