4-34 Protection
and
Control BE1-CDS220
Retrieving Breaker Failure Status from the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6,
Reporting and Alarm
Functions, General Status Reporting,
for more information.
LOGIC TIMERS
62 - General Purpose Logic Timers
BE1-CDS220 relays provide two general-purpose logic timers, which are extremely versatile. Each can be
set for one of five modes of operation to emulate virtually any type of timer. Each function block has one
output (62 or 162) that is asserted when the timing criteria has been met according to the BESTlogic
mode setting. Figure 4-30 shows the 62 function block as an example. Each mode of operation is
described in detail in the following paragraphs.
Figure 4-30. General Purpose Logic Timers Logic Block
An
INI
(initiate) logic input is provided to start the timing sequence.
A
BLK
(block) logic input is provided to block operation of the timer. When this expression is TRUE, the
function is disabled.
Each timer has a
T1
time setting and a
T2
time setting. The functioning of these settings is dependent
upon the type of timer as specified by the mode setting in BESTlogic.
If the target is enabled for the function block, the target reporting function will record a target when the
timer output is TRUE and the fault recording function trip logic expression is TRUE. See Section 6,
Reporting and Alarm Functions, Fault Reporting
, for more details on the target reporting function.
Mode 1, PU/DO (Pickup/Dropout Timer)
The output will change to logic TRUE if the
INITIATE
input expression is TRUE for the duration of
PICKUP time delay setting T1. See Figure 4-31. If the initiate expression toggles to FALSE before time
T1, the T1 timer is reset. Once the output of the timer toggles to TRUE, the
INITIATE
input expression
must be FALSE for the duration of DROPOUT time delay setting T2. If the
INITIATE
input expression
toggles to TRUE before time T2, the output stays TRUE and the T2 timer is reset.
D2843-08
10-23-03
Figure 4-31. Mode 1, PU/DO (Pickup/Dropout Timer)
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......