13-6
Testing And Maintenance
BE1-CDS220
NOTE
Each BE1-CDS relay is delivered with the eight sensing jumpers installed for operation in
the lower end of the control voltage range (pins 1 and 2 shorted). For contact sensing
inputs at the upper end of the control voltage range, change the jumpers to short pins 2
and 3 or completely remove the jumper. For more information see Section 12, Installation,
Contact Sensing Input Jumpers.
Step 1. Verify that the position of the contact sensing jumpers is correct before applying wetting
voltage to any input contacts.
Step 2. Use Table 13-2 as a reference. Apply an external voltage source above the appropriate
voltage turn-on range listed in Table 13-2 but below the power supply maximum voltage to
contact sensing inputs IN1, IN2, IN3, IN4, IN5, IN6, IN7, and IN8.
Table 13-2. Input Contact Wetting Voltage
Turn-On Range
Nominal Control
Voltage (Range)
Pin 1 - Pin 2
Pin 2 - Pin 3
24 Vdc (17 to 32 Vdc)
13 to 19 Vdc
N/A
48/125 Vac/Vdc
(35 to 150 Vdc/55 to 135 Vac)
26 to 38 Vdc
69 to 100 Vdc
125/250 Vac/Vdc
(90 to 300 Vdc/90 to 270 Vac)
69 to 100 Vdc
138 to 200 Vdc
Step 3. To verify that all inputs have been detected, transmit the command RG-INPUT to retrieve
INPUT (12345678) information or, alternatively, transmit the command RG-STAT and review
the response at the tail end of the line INPUT (12345678). You may also view the input status
on HMI screen 1.4.1, \STAT\OPER\INPUT.
Step 4.
Transmit the commands ACCESS=, CS-OUT=ENA, CO-OUT=ENA, EXIT, and YES to enable
the output control override capability of the relay in order to pulse each output contact.
NOTE
If your relay is supplied with the HMI option, skip steps 5 and 6 and proceed directly to
Step 7.
Step 5.
Using Table 13-3 as a guide, transmit the commands listed and verify that the appropriate
output contacts change state. When the operate command is transmitted, the corresponding
output changes state for 200 milliseconds and returns to the normal state. An ohm-meter or
continuity tester may be used to monitor the output contacts. Remember, you have to gain
access (as in Step 4) before you begin issuing commands and again if the access time-out
expires.
Step 6.
If desired, you may disable the control override capability by transmitting the commands
ACCESS=, CS-OUT=DIS, CO-OUT=DIS, EXIT, and YES to the relay.
Table 13-3. Output Control Override Commands
Output Terminals
Commands
ALARM (N.C.)
C1 and C2
CS-OUTA=P,CO-OUTA=P
OUT1 (N.O.)
C3 and C4
CS-OUT1=P,CO-OUT1=P
OUT2 (N.O.)
C5 and C6
CS-OUT2=P,CO-OUT2=P
OUT3 (N.O.)
C7 and C8
CS-OUT3=P,CO-OUT3=P
OUT4 (N.O.)
C9 and C10
CS-OUT4=P,CO-OUT4=P
OUT5 (N.O.)
C11 and C12
CS-OUT5=P,CO-OUT5=P
OUT6 (NC/NO)
C13, C14, and C15
CS-OUT6=P,CO-OUT6=P
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......