BE1-CDS220
Testing And Maintenance
13-57
Table 13-52. Time Overcurrent 51 Element Test Values
Relay Trip
Sensing Input Type
Time Dial
Applied Current
Lower Limit
Higher Limit
1 A
0.5
1.50 A
0.748 sec
0.827 sec
5.00 A
0.190 sec
0.240 sec
5.0
1.50 A
7.244 sec
8.007 sec
5.00 A
1.798 sec
1.988 sec
9.9
1.50 A
14.318 sec
15.825 sec
5.00 A
3.535 sec
3.907 sec
5 A
0.5
7.5 A
0.748 sec
0.827 sec
25.0 A
0.190 sec
0.240 sec
5.0
7.5 A
7.244 sec
8.007 sec
25.0 A
1.798 sec
1.988 sec
9.9
7.5 A
14.318 sec
15.825 sec
25.0 A
3.535 sec
3.907 sec
Step 6.
Repeat Steps 3, 4, and 5 for all current and time dial settings listed (using the command S0-
51P, 51N, and 51Q or, if your relay is supplied with the HMI option, by navigating to screen
\PROT\SG0\51\51 to edit the 51P, 51N, and 51Q settings) and optionally, reconnect the
current source to B-phase (B3, B4) and C-phase (B5, B6) inputs to test the response of all
phases for each succeeding test.
Step 7.
(Optional) Repeat Steps 2 through 6 for B and C phase elements unless each phase was
tested in previous steps. If so, skip this step and proceed to Step 8.
Step 8.
(Optional) Repeat Steps 1 through 7 for the 151 and 251 elements respectively. Use Table 13-
51 or 13-52 as a reference for substituting the commands used in Step 1.
Step 9.
(Optional) Repeat steps 1 through 8 for the 51, 151, and 251 elements in setting groups 1, 2,
and 3. Use the following information as a guide to program the 51/151/251 elements in higher
order setting groups.
In order to program the pickup of the elements in a higher order setting group, you would
replace the
0
in the S
0
-51P, S
0
-51N, and S
0
-51Q commands in Table 13-50 with a 1, 2, or 3
for setting groups 1, 2, or 3. Or, if your relay is supplied with the HMI option, you can program
each set of values by navigating to the appropriate setting group screen \PROT\SGn\51\51,
where n is equal to the setting group you desire. Refer to the CS/CO-GROUP command in
Section 4,
Protection and Control Functions
for more information on changing the active setting
group.
To change from group 0 to group 1, execute the following commands.
CS-GROUP=1
select setting group 1
CO-GROUP=1 execute setting group 1
Using the basic information in Table 13-50, program the pickup of the elements for setting
group 1 and, optionally, proceed with the testing.
Breaker Failure
Purpose:
To verify the operation of the breaker failure (BF) function.
Reference Commands: SL-BF, SP-BF
Step 1.
Prepare the BF function block for testing by transmitting the commands in Table 13-53 to the
relay.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......