BE1-CDS220
Time Overcurrent Characteristic Curves
A-3
Table A-2. Characteristic Curve Cross-Reference
Curve Curve
Name
Drawing No.
Similar To
S1
S, S1, Short Inverse
99-1369
ABB CO-2
S2
S2, Short Inverse
99-1595
GE IAC-55
L1
L, L1, Long Inverse
99-1370
ABB CO-5
L2
L2, Long Inverse
99-1594
GE IAC-66
D
D, Definite Time
99-1371
ABB CO-6
M
M, Moderately Inverse
99-1372
ABB CO-7
I1
I, I1, Inverse Time
99-1373
ABB CO-8
I2
I2, Inverse Time
99-1597
GE IAC-51
V1
V, V1, Very Inverse
99-1374
ABB CO-9
V2
V2, Very Inverse
99-1596
GE IAC-53
E1
E, E1, Extremely Inverse
99-1375
ABB CO-11
E2
E2, Extremely Inverse
99-1598
GE IAC-77
A
A, Standard Inverse
99-1621
BS, IEC Standard Inverse
B
B, Very Inverse (I
2
t)
99-1376
BS, IEC Very Inverse (I
2
t)
C
C, Extremely Inverse (I
2
t)
99-1377
BS, IEC Extremely Inverse (I
2
t)
G
G, Long Time Inverse (I
2
t)
99-1622
BS, IEC Long Time Inverse (I
2
t)
F
Fixed Time
N/A
N/A
P
Programmable N/A
N/A
Time Dial Setting Cross-Reference
Although the time characteristic curve shapes have been optimized for each relay, time dial settings of
Basler Electric relays are not identical to the settings of electromechanical induction disk overcurrent
relays. Table A-3 helps you convert the time dial settings of induction disk relays to the equivalent setting
for Basler Electric relays. Enter time dial settings using BESTCOMS, S<g>-
51P/51N/51Q/151P/151N/151Q/251P/251N/251Q ASCII commands, or human-machine interface (HMI)
Screens 5.x.4.1 (51P/N/Q), 5.x.4.2 (151P/N/Q), and 5.x.4.3 (251P/N/Q). For more information, refer to
Section 4, Protection and Control, Overcurrent Protection, 51 - Time Overcurrent Protection.
Using Table A-3
Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial calculator
function for each time dial setting. The equivalent Basler Electric time dial setting was then entered into
the cross-reference table.
If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electromechanical setting
and the Basler Electric setting.
Basler Electric relays have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial
setting for the electromechanical maximum setting is provided in the cross-reference table even if it
exceeds 9.9. This allows interpolation as noted above.
Basler Electric time current characteristics are determined by a linear mathematical equation. The
induction disk of an electromechanical relay has a certain degree of non linearity due to inertial and friction
effects. For this reason, even though every effort has been made to provide characteristic curves with
minimum deviation from the published electromechanical curves, slight deviations can exist between
them.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......