BE1-CDS220 Protection
and
Control
4-27
Figure 4-23. Overcurrent Screen, 51 Tab
Table 4-13. Operating Settings for Time Overcurrent
Range
Setting
5 A
1 A
Increment
Unit of
Measure
Default
Pickup
0 = Disabled
0.5 to 16
0 = Disabled
0.1 to 3.2
0.01 for 0.01 to 9.99
0.1 for 10.0 to 16.0
Sec. Amps
0
Time Dial
0.0 to 9.9
0.1
N/A
0
Curve
See Appendix A
N/A
N/A
V2
Example 1.
Make the following settings to the Phase 51P time overcurrent element in BESTCOMS.
Refer to Figure 4-23.
Pickup:
10 secondary amps
Time Dial: 3.0
Curve:
S1R
Retrieving Time Overcurrent Status from the Relay
The status of each logic variable can be determined through the ASCII command interface using the RG-
STAT (report general-status) command. See Section 6, Reporting and Alarm Functions, General Status
Reporting, for more information.
Programmable Curves
Time current characteristics for trip and reset programmable curves are defined by Equation 4-7 and
Equation 4-8 respectively. These equations comply with IEEE standard C37.112-1996. The curve specific
coefficients are defined for the standard curves as listed in Appendix A, Time Overcurrent Characteristic
Curves. When time current characteristic curve P is selected, the coefficients used in the equation are
those defined by the user. Definitions for these equations are provided in Table 4-16.
Equation 4-7. Time OC Characteristics for Trip
K
BD
C
M
AD
T
N
T
+
+
−
=
Equation 4-8. Time OC Characteristics for Reset
1
2
−
=
M
RD
T
R
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......