Testing And Maintenance
13-51
Step 1.
Connect a current source to terminals B1 and B2 (A phase input 1).
Step 2.
To initially prepare the 50T/150T/250T elements for testing, transmit the commands in Table
13-40 to the relay.
Table 13-40. 50T/150T/250T Overcurrent Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm
overwrite
SL-N=PU50
Name custom logic for this test
SL-50T=1,0 Enables
50TP/50TN/50TQ, CT input 1
SL-VO1=50TPT
Enables OUT1 to close for 50T P trip
SL-VO2=50TNT
Enables OUT2 to close for 50T N trip
SL-VO3=50TQT
Enables OUT3 to close for 50T Q trip
SG-CT1=1,WYE,NA,0
Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=50TPT+
50TNT,+50TQ5
0TNPU,+50TQN,0
Enable 50TP+50TN+50TQ to log and trigger fault
recording
E Exit
Y Save
settings
Step 3.
Send the first appropriate row of the setting commands S0-50TP, S0-50TN, and S0-50TQ from
Table 13-41 to the relay. If your relay is supplied with the HMI option, you may also go to the
front panel interface screen \PROT\SG0\50T\50T and edit the S0-50TP, S0-50TN, and S0-
50TQ settings.
Table 13-41. Instantaneous 50T Element Test Values
Sensing
Input Type
Phase
Negative
Sequence
Neutral
Comments
5 A
S0-50TP=0.5,0
S0-50TQ=0,0 S0-50TN=0.5,0
Note
1
S0-50TP=5.0,0
S0-50TQ=1.67,0 S0-50TN=5.0,0
Note
2
S0-50TP=25.0,0
S0-50TQ=8.33,0 S0-50TN=25.0,0
Note
2
1 A
S0-50TP=0.1,0
S0-50TQ=0,0 S0-50TN=0.1,0
Note
1
S0-50TP=1.0,0
S0-50TQ=0.33,0 S0-50TN=1.0,0
Note
2
S0-50TP=5.0,0
S0-50TQ=1.67,0 S0-50TN=5.0,0
Note
2
Notes for Table 13-41:
1.
Sets 50TP and 50TN to pickup at 0.5 amperes test current, and 50TQ is disabled.
2.
Sets all 50T<x> to pickup at 0.5 amperes test current.
3.
See Sidebar 13-10 for more information on negative sequence pickup.
Step 4.
Slowly ramp up current on the phase A input until OUT1, OUT2, and OUT3 close. (In
accordance with Note 1 for Table 13-41, OUT3 will not close when 50TQ is disabled.) Verify
that pickup occurred within the specified accuracy of the relay as listed in Table 13-42.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......