BE1-CDS220 General
Information
1-1
SECTION 1
•
GENERAL INFORMATION
DESCRIPTION
The BE1-CDS220 Current Differential System is an economical, microprocessor based, multifunction
system that provides two-input, three-phase percentage differential with harmonic restraint, three-phase,
ground, and negative sequence overcurrent protection with control, breaker failure, breaker monitoring,
transformer monitoring, and metering functions in an integrated system with communications. The
BE1-CDS Current Differential System is intended for use in any low impedance current differential
protection application including transformer, generator, motor, and bus protection. Four setting groups are
provided for adaptive relaying with automatic selection logic for cold load pickup and/or dynamic setting
group changes.
BE1-CDS relays have eight programmable contact sensing inputs, six programmable outputs, and one
alarm output. Outputs can be assigned various functions by logical programming to perform protection,
control, or indicator operations. For example, protection functions could cause a protective trip operation.
Control functions could cause a manual trip, manual close or automatic reclose operation. Indicators
could be relay fail, setting group one enable, setting group two enable, and others.
Protection scheme designers may select from a number of pre-programmed logic schemes that perform
the most common protection and control requirements or create a custom scheme using BESTlogic.
A Quick Start, Section 2, provides BE1-CDS Current Differential System users with a simplified How to
Get Started procedure.
FEATURES
The BE1-CDS220 relay includes many features for the protection, monitoring, and control of power
system equipment such as transformers, breakers, buses, generators, and motors. These features
include protection and control functions, metering functions, and reporting and alarm functions. A highly
flexible programmable logic system called BESTlogic allows the user to apply the available functions with
complete flexibility and customize the system to meet the requirements of the protected power system.
Programmable I/O, extensive communications features, and an optional advanced HMI (Human Machine
Interface) provide easy access to the features provided. BE1-CDS220 relay users with personal
computers (PC) have another easy access means to communicate, program, control, and monitor
relay/system performance. That means is BESTCOMS for BE1-CDS220. BESTCOMS is a Windows
based software application that enhances communication between the PC user and the BE1-CDS220
relay. This software is provided free with every BE1-CDS220 relay. Another software application tool is
BESTWAVE. BESTWAVE is a utility program to view standard COMTRADE (Common Format for
Transient Data Exchange) files and Basler UMOS (Utilities Management Operating System) files captured
by the Basler Electric multifunction relays. This software is available free of charge through the web site at
http://www.basler.com or Customer Service at the Highland, Illinois manufacturing facility.
The following information summarizes the features included in this multifunction device. The organization
of this information outlines organization of the rest of the manual. Each feature, along with how to set it up
and how to use the outputs is described in complete detail in the later sections of this manual.
Input and Output Functions
Power System Measurement Functions
•
Two sets of three-phase currents are digitally sampled and digitally filtered. The fundamental,
second, and fifth harmonics are extracted using a Discrete Fourier Transform (DFT) algorithm for
use by all of the current based functions.
•
Neutral (residual) and negative sequence current magnitudes are derived from each set of three-
phase currents.
•
Each set of three-phase currents can be phase-shift and tap compensated for use in transformer
differential applications.
•
The digital sampling rate tracks the measured frequency to provide high accuracy at frequencies
other than nominal frequency to make this relay ideally suited for applications such as generator,
motor, and generator step-up transformer differential protection.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......