Advanced Logic Control Relay & Power Supply Cabinet

INSTALLATION INSTRUCTIONS

Electrified Locks, Relays and Timers

THIS PACKAGE INCLUDES:  

1. DESCRIPTION 

The CX-33PS is designed to make installations easier and quicker 

by having Camden’s advanced relay logic controller (CX-33) pre-

wired to a color-coded set of labeled terminal strips. CX-33's 15 

operating modes will handle a wide variety of applications from 

Vestibule openings to Card Access and Alarm Integration.
Its attractive metal cabinet also provides a pre-mounted 2 amp 

12/24 VDC filtered and regulated power supply with enough 

current to run options such as Camden’s Aura illumination 

boards, Emergency Call kits, and lock power. Camden CX-33PS 

provides a clean and organized location for field wiring. 

Backed by Camden’s 3-year warranty.

2. SPECIFICATIONS

Voltage 

AC Input: 12V to 28V DC  Output: 12  or 24V

Current Supply

2 Amps

Battery Backup

Gel Type Battery (not supplied)

LED Indicator

AC and DC Output

Temperature

Operating:

 0° C to 49° C (32° F to 120° F)

Storage:

 - 20° C to 70° C ( - 4° F to 158° F )

Inputs

(4) Dry, (1) Wet 5V to 120V AC/DC, 

Non-Polarity Optically Isolated

Outputs

(3) Form 'C' (SPDT), 3 Amps @ 24V DC

Time Delay

Hold 1 Timer: 0 to 50 seconds Delay 1 

Timer: 0 to 15 seconds 
Hold 2 Timer: 0 to 50 seconds Delay 2 

Timer: 0 to 60 seconds 
Hold 3 Timer: 0 to 50 seconds 

Delay on Activate: 0 to 10 seconds

Dimensions

7-7/8" W x 11-1/16" H x 2-13/16" D 

(200mm x 281mm x 72mm)

3. DIMENSIONS 

4. INSTALLATION

IMPORTANT: Do not apply power to the unit until you have read 

the instructions fully and made the required adjustments.

Mounting

The CX-33PS cabinet should be mounted in a clean dry location 

out of direct contact with the elements. 
Using a level, position the CX-33PS cabinet at the desired 

location and mark the four holes needed to mount it to the 

wall. Using the supplied wall anchors (concrete or drywall) 

and screws, fasten the CX-33PS to the wall.

Wiring

IMPORTANT: Confirm the electrical panels breaker you are 

going to be using is currently off. Do not wire the primary 

terminals of the transformer until the secondary terminals 

are connected first. 
Wiring the CX-33PS will be based on which one of the 15 available 

modes is selected to best suit your application (the modes 

are discussed in detail in the CX-33 installation manual). Once 

the mode is chosen, wiring the field devices is simplified by 

connecting each item to its own labeled input. There are 

dedicated inputs for PUSH TO OPEN/PUSH TO LOCK push 

plates (interior/exterior), door contacts (provides door status to 

the CX-33PS), dry and wet trigger inputs (for Access Control/

Alarm/Fire integration), and a VAC input from the supplied 

step-down transformer.

(1)  Metal Cabinet 
(1)  Hardware Kit

(1)  CX-TRX-5024 50VA 
      Class 2 transformer

2-13/16" (72mm)

7-7/8" (200mm)

11-1/16" (281mm)

(1)  Pre-wired CX-33 Relay 
(1)  2 Amp Power Supply

Содержание CX-33PS

Страница 1: ...0 to 50 seconds Delay on Activate 0 to 10 seconds Dimensions 7 7 8 W x 11 1 16 H x 2 13 16 D 200mm x 281mm x 72mm 3 DIMENSIONS 4 INSTALLATION IMPORTANT Do not apply power to the unit until you have r...

Страница 2: ...n normally open or normally closed contact N O or N C 2 Set Dry Input 2 to activate on normally open or normally closed contact N O or N C 3 Set Dry Input 3 to activate on normally open or normally cl...

Страница 3: ...n one direction using what we call mixed mode triggering Some popular applications include basic strike and operator installations smoke evacuation stairwell doors or latching applications Refer to Di...

Страница 4: ...e made In addition you can add a Delay on activate or nuisance delay to this mode by setting time via Step 8 of the Program Mode If this feature is used any input will have to be held for at least the...

Страница 5: ...g adjustments may need to be made It is NOT recommended to add the Delay on activate or nuisance delay feature in this mode Once the desired operation is achieved proceed to Section 4 Page 9 for Syste...

Страница 6: ...am 10 Page 21 for the following connections SAM Circuit Connect the momentary activating switch es to DRY 3 input The door mounted sensor connects to DRY 2 input and the magnetic contact switch connec...

Страница 7: ...status LED light When the Reset button connected to Input 4 is momentarily depressed the door unlocks and the system resets Refer to Diagram 7a Page 26 for connections The allactive switches and Lock...

Страница 8: ...test it This should be checked on a daily basis 3 Instruct the owner on what to do if the door or any of its components become damaged 4 Strongly recommend to the owner that the complete entry be insp...

Страница 9: ...NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 1 CX 33 Mode 120 VAC Transformer CX TRX 5024 24 VAC 50 VA PUSH TO OPEN FIRE A Momentary Input La...

Страница 10: ...and open when door opens 2 If electric lock is not used set H1 and D1 timers to 0 D2 is not used in this mode Activating Switch es Door 1 Optional Electric Lock Door 1 MOV N C N C Magnetic Contact Swi...

Страница 11: ...is not used set H1 and D1 timers to 0 D2 is not used in this mode 3 Walk away feature is used with locks only not operators Otherwise set H2 H3 Timers to 0 Activating Switch es Door 1 Optional Electri...

Страница 12: ...DATE 04 17 2020 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 CAMDEN DOOR CONTROLS Door 1 AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 CO...

Страница 13: ...NPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 4 CX 33 Mode 120 VAC Trans...

Страница 14: ...ys unlocks and opens door 5 Fire Alarm Input 4 fires relays 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPU...

Страница 15: ...lways unlocks and opens door 5 Fire Alarm Input 4 fires relays 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator N O Maintained Dry Contact Only Inside Switch Fai...

Страница 16: ...ail Safe Electric Strike Shown If Fail Secure lock is used wire to RELAY 1 NC Outside Push To Open MOV N C AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY...

Страница 17: ...wire to RELAY 1 NC Wire MOV supplied directly to strike or magnet Outside Push To Open MOV AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM...

Страница 18: ...afe lock is used wire to RELAY 1 NC Wire MOV supplied directly to strike or magnet MOV N C AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM...

Страница 19: ...3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 9 CX 33 Mode 120 VAC Transformer CX TRX 5024 24 VAC 50 VA PUSH TO OPEN Door Beams rail mounted Power required for beams not shown PUSH TO O...

Страница 20: ...ing network circuit and are optional 2 SAM Circuit complies with ANSI A156 19 when wired as shown 3 Sensor is only active after Switch is pressed and remains active until door closes 4 The CX 33 also...

Страница 21: ...ll switch inputs are disabled 3 Sensor is only active after Switch is pressed and remains active until door closes 4 All items in dashed lines are optional MOV Magnetic Contact Switch N C AC AC DRY 1...

Страница 22: ...closes the Mag Lock is released and the wall switch inputs are disabled 3 All items in dashed lines are optional Magnetic Contact Switch Fire Alarm Input N C dry contact unlocks door and disables norm...

Страница 23: ...DOOR CONTROLS AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU...

Страница 24: ...electric lock after release of the Push Panic Switch 4 The Bypass or Shunt switch Input and the Fire Panel Input essentially do the same thing activate relay s 2 3 Magnetic Contact Switch Shunt Bypas...

Страница 25: ...active when the strike is energized 4 Inside switch always unlocks and opens door Door 1 Operator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC REL...

Страница 26: ...ly Activating Switch activates relay 3 only Door 1 Operator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3...

Отзывы: