CX-33PS Advanced Logic Control Relay & Power Supply Cabinet

INSTALLATION INSTRUCTIONS

LOR Circuit:
A parallel connection is made to the two motor wires running 

from the Operator (motor) to its control. If the motor is AC, 

then polarity is not an issue. The CX-33 is triggered by the AC 

voltage going from high to low.
If the motor is DC, then the wires are polarity sensitive. If 

Relay 3 LED doesn’t illuminate when the door is closing, then 

just reverse the two terminal connections at the CX-33.
Input 1 is for the N.O. relay contacts of the photo beam. The 

beams are typically mounted at the end of guide rails and 

designed to reset the LOR in the event anyone should walk 

into the swing path when the door is in the closing cycle.
Relay 3 output is to be connected in SERIES with the safety 

device and the Safety Circuit of the operator.
Optional Switching Network:
Wire the activating device(s) to DRY 1, DRY 2 or DRY 3 

terminals. Wire the outputs as shown to Relays 1 & 2.
Once input and output connections are made, program the 

unit according to the General Programming Instructions on 

page 1, and walk-test the installation. Timing adjustments 

may need to be made.
It is NOT recommended to add the “Delay-on-activate” (or 

nuisance delay) feature in this mode. Once the desired 

operation is achieved, proceed to Section 4, (Page 9) for 

System Inspection Instructions.

Section 3 K
Low Energy SAM Plus  (Mode 10)

This mode combines a Low-Energy Secondary Activation 

Module (SAM) with a switching network (aka make/break 

relay). Utilizing a door position switch input, this mode 

enables or disables a door mounted presence sensor. The 

sensor is put into the circuit when a wall switch is pressed 

(a Knowing Act). This allows an object or person in the path 

of the door to be detected. The door will not close until the 

object or person leaves the door swing path. The sensor 

remains in the circuit until the door is closed.
When the door is opened manually, the safety sensor is not 

in the circuit and the door operator functions as a manual 

door closer. A unique feature of the CX-33 is the automatic 

reset feature. If a switch has been pressed, but the door 

has not opened within 60 seconds (because it is locked, for 

instance), the unit resets, reducing wear and tear on the lock 

and operator.
In addition, one input and two relays are provided for the 

switching network function.
Refer to Diagram 10, (Page 21) for the following connections.
SAM Circuit:
Connect the momentary activating switch(es) to DRY 3 input. 

The door mounted sensor connects to DRY 2 input, and the 

magnetic contact switch connects to DRY 4 input. The contact 

switch circuit must be closed when the door is closed, and 

open when the door opens.

Relay 3 output is to be connected to the Activate circuit of the 

door operator.
Optional Switching Network:
Wire the activating device(s) to DRY 1 terminals. 

Wire the outputs as shown to Relays 1 & 2.
Once input and output connections are made, program the 

unit according to the General Programming Instructions on 

page 1, and walk-test the installation. Timing adjustments 

may need to be made.
It is NOT recommended to add the “Delay-on-activate” (or 

nuisance delay) feature in this mode.
Once the desired operation is achieved, proceed to Section 4, 

(Page 9) for System Inspection Instructions.

Section 3 L
Mag Lock with N.O. Fire Alarm  (Mode 11)

Commonly seen in hospital corridors, this version of a 

switching network (make/break relay) is specifically designed 

for doors with mag locks.
A wall switch signals the relay, which unlocks, and opens the 

door for an adjustable time. Utilizing the door position switch, 

the CX-33 will not re-apply power to the magnetic lock until 

the door is fully closed. The relay also provides for a normally 

open Fire Alarm input, which when activated, unlocks the 

door and disables the wall switch inputs.
Refer to Diagram 11, (Page 22) for the following connections:
Momentary switches connect to DRY 1 and/or WET terminals.
Maintained devices connect to DRY 2 input (optional).
The N.O. Fire Alarm signal is wired to DRY 3 input, and the 

Door Position Switch connects to DRY 4 input. The circuit 

must be closed when the door is closed, and open when the 

door opens.
The magnetic lock connects to the Common and N.C terminals 

of Relay 1. The door operator connects to the Common and 

N.O. terminals of Relay 2. Relay 3 output is optional.
Once input and output connections are made, program the 

unit according to the General Programming Instructions on 

page 1, and walk-test the installation. Timing adjustments 

may need to be made.
It is NOT recommended to add the “Delay-on-activate” (or 

nuisance delay) feature in this mode!
Once the desired operation is achieved, proceed to Section 4, 

(Page 9) for System Inspection Instructions.

Section 3 M
Mag Lock with N.C. Fire Alarm (Mode 12)

This mode is identical to Mode 11 (Section 3L) except the Fire 

Alarm input is a N.C. circuit (rather than N.O.). See previous 

section for wiring and adjustments, & refer to Diagram 12, 

(Page 23).

Содержание CX-33PS

Страница 1: ...0 to 50 seconds Delay on Activate 0 to 10 seconds Dimensions 7 7 8 W x 11 1 16 H x 2 13 16 D 200mm x 281mm x 72mm 3 DIMENSIONS 4 INSTALLATION IMPORTANT Do not apply power to the unit until you have r...

Страница 2: ...n normally open or normally closed contact N O or N C 2 Set Dry Input 2 to activate on normally open or normally closed contact N O or N C 3 Set Dry Input 3 to activate on normally open or normally cl...

Страница 3: ...n one direction using what we call mixed mode triggering Some popular applications include basic strike and operator installations smoke evacuation stairwell doors or latching applications Refer to Di...

Страница 4: ...e made In addition you can add a Delay on activate or nuisance delay to this mode by setting time via Step 8 of the Program Mode If this feature is used any input will have to be held for at least the...

Страница 5: ...g adjustments may need to be made It is NOT recommended to add the Delay on activate or nuisance delay feature in this mode Once the desired operation is achieved proceed to Section 4 Page 9 for Syste...

Страница 6: ...am 10 Page 21 for the following connections SAM Circuit Connect the momentary activating switch es to DRY 3 input The door mounted sensor connects to DRY 2 input and the magnetic contact switch connec...

Страница 7: ...status LED light When the Reset button connected to Input 4 is momentarily depressed the door unlocks and the system resets Refer to Diagram 7a Page 26 for connections The allactive switches and Lock...

Страница 8: ...test it This should be checked on a daily basis 3 Instruct the owner on what to do if the door or any of its components become damaged 4 Strongly recommend to the owner that the complete entry be insp...

Страница 9: ...NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 1 CX 33 Mode 120 VAC Transformer CX TRX 5024 24 VAC 50 VA PUSH TO OPEN FIRE A Momentary Input La...

Страница 10: ...and open when door opens 2 If electric lock is not used set H1 and D1 timers to 0 D2 is not used in this mode Activating Switch es Door 1 Optional Electric Lock Door 1 MOV N C N C Magnetic Contact Swi...

Страница 11: ...is not used set H1 and D1 timers to 0 D2 is not used in this mode 3 Walk away feature is used with locks only not operators Otherwise set H2 H3 Timers to 0 Activating Switch es Door 1 Optional Electri...

Страница 12: ...DATE 04 17 2020 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 CAMDEN DOOR CONTROLS Door 1 AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 CO...

Страница 13: ...NPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 4 CX 33 Mode 120 VAC Trans...

Страница 14: ...ys unlocks and opens door 5 Fire Alarm Input 4 fires relays 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPU...

Страница 15: ...lways unlocks and opens door 5 Fire Alarm Input 4 fires relays 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator N O Maintained Dry Contact Only Inside Switch Fai...

Страница 16: ...ail Safe Electric Strike Shown If Fail Secure lock is used wire to RELAY 1 NC Outside Push To Open MOV N C AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY...

Страница 17: ...wire to RELAY 1 NC Wire MOV supplied directly to strike or magnet Outside Push To Open MOV AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM...

Страница 18: ...afe lock is used wire to RELAY 1 NC Wire MOV supplied directly to strike or magnet MOV N C AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM...

Страница 19: ...3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU UP DOWN 0 0 9 CX 33 Mode 120 VAC Transformer CX TRX 5024 24 VAC 50 VA PUSH TO OPEN Door Beams rail mounted Power required for beams not shown PUSH TO O...

Страница 20: ...ing network circuit and are optional 2 SAM Circuit complies with ANSI A156 19 when wired as shown 3 Sensor is only active after Switch is pressed and remains active until door closes 4 The CX 33 also...

Страница 21: ...ll switch inputs are disabled 3 Sensor is only active after Switch is pressed and remains active until door closes 4 All items in dashed lines are optional MOV Magnetic Contact Switch N C AC AC DRY 1...

Страница 22: ...closes the Mag Lock is released and the wall switch inputs are disabled 3 All items in dashed lines are optional Magnetic Contact Switch Fire Alarm Input N C dry contact unlocks door and disables norm...

Страница 23: ...DOOR CONTROLS AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3 COM RELAY 3 NO RELAY 3 NC VDC VDC DISPLAY MENU...

Страница 24: ...electric lock after release of the Push Panic Switch 4 The Bypass or Shunt switch Input and the Fire Panel Input essentially do the same thing activate relay s 2 3 Magnetic Contact Switch Shunt Bypas...

Страница 25: ...active when the strike is energized 4 Inside switch always unlocks and opens door Door 1 Operator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC REL...

Страница 26: ...ly Activating Switch activates relay 3 only Door 1 Operator AC AC DRY 1 INPUT DRY 2 INPUT DRY 3 INPUT DRY 4 INPUT WET INPUT RELAY 1 COM RELAY 1 NO RELAY 1 NC RELAY 2 COM RELAY 2 NO RELAY 2 NC RELAY 3...

Отзывы: