background image

 

IL04906001E

 

Effective 03/07

1

 

IL04906001E

 

Effective 03/07

1

 

Instructions for D85 Series Alternating Relays

 

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE.

!

WARNING

 

Potentially hazardous voltages are present. Turn off all power supplying 
this equipment before connecting or disconnecting wiring.

 

Installation & Wiring

 

Mount the appropriate 8 or 11 pin octal socket in a suitable enclosure. Wire the socket per one of the 
diagrams in Figure 1. Any type of switch (float, manual, timing relay, pressure, or one with an isolated 
contact) can be used.

 

NOTE:

 

If you are using the same Control Voltage for both the Alternating Relay and the two loads, you 
must add a jumper between Terminals 1 & 5 on the SPDT unit or Terminals 2, 6 & 10 on the 
DPDT unit. If using multiple switches on the DPDT cross-wired units, check to see the proper 
sequence of switch closures is followed, i.e., LEAD before LAG, STOP before LEAD, etc.

 

Figure 1. 

 

Wiring Diagrams

 

If the unit has the low-profile selector switch, set this switch to “ALTERNATE” for normal operation. In 
this mode, the unit will operate as a normal Alternating Relay, alternating between the two loads on 
each subsequent closing and opening of the control switch. Setting the selector switch to either “LOAD 
A” or “LOAD B” will lock the unit to either one of the loads. By locking the Alternating Relay to one load, 
the other load can be removed for service without rewiring the first load for continuous operation.

!

WARNING

 

When the selector switch is locked in either the LOAD A or LOAD B 
position, it does not disconnect voltage from the equipment to be serviced.

 

Typical Installations

 

SPDT and DPDT Alternating Relays

 

Figure 2. 

 

Typical Installations for SPDT and DPDT Alternating Relays

 

In the OFF state (Standard Installation), the Control Switch is open, the Alternating Relay is in the 
LOAD A position, and both loads (M1 & M2) are off. When the Control Switch closes, it energizes the 
first load (M1). The red LED marked “LOAD A” glows. As long as the Control Switch remains closed, 
M1 remains energized. When the Control Switch opens, the first load (M1) is turned off and the Alter-
nating Relay toggles to the LOAD B position. When the Control Switch closes again, it energizes the 
second load (M2). The red LED marked “LOAD B” glows. When the Control Switch opens, the second 

Load A: Pi

n

 2

Load B: Pi

n

 8

1

4

I

n

put

Voltage

Co

n

trol

S

witch

L2

L1

3

6

2

7

8

5

1

Load A: Pi

n

s 3 or 11

Load B: Pi

n

s 1 or 9

L2

L1

11

I

n

put

Voltage

Co

n

trol

S

witch

4

8

3

9

6

2

10

7

5

1

Lead

Lag

Load

B

Load

A

L1

L2

8

I

n

put

Voltage

4

3

6

2

7

5

1

Lead

Lag

Load

B

Load

A

L1

L2

8

I

n

put

Voltage

S

top

4

3

6

2

7

5

SPDT

DPDT

DPDT Cross-Wired

DPDT Cross-Wired for 3 Switches

L1

S

PDT

S

PDT

Co

n

trol

S

witch

Co

n

trol

S

witch

O/L

O/L

1

2

8

3

4

5

L1

L2

1

2

3

4

5

Off

M1

M1

M1

M2

L2

M2

M2

8

Standard Installation

Anti-Bounce Installation

 

Instructions for D85 Series Alternating Relays

 

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE.

!

WARNING

 

Potentially hazardous voltages are present. Turn off all power supplying 
this equipment before connecting or disconnecting wiring.

 

Installation & Wiring

 

Mount the appropriate 8 or 11 pin octal socket in a suitable enclosure. Wire the socket per one of the 
diagrams in Figure 1. Any type of switch (float, manual, timing relay, pressure, or one with an isolated 
contact) can be used.

 

NOTE:

 

If you are using the same Control Voltage for both the Alternating Relay and the two loads, you 
must add a jumper between Terminals 1 & 5 on the SPDT unit or Terminals 2, 6 & 10 on the 
DPDT unit. If using multiple switches on the DPDT cross-wired units, check to see the proper 
sequence of switch closures is followed, i.e., LEAD before LAG, STOP before LEAD, etc.

 

Figure 1. 

 

Wiring Diagrams

 

If the unit has the low-profile selector switch, set this switch to “ALTERNATE” for normal operation. In 
this mode, the unit will operate as a normal Alternating Relay, alternating between the two loads on 
each subsequent closing and opening of the control switch. Setting the selector switch to either “LOAD 
A” or “LOAD B” will lock the unit to either one of the loads. By locking the Alternating Relay to one load, 
the other load can be removed for service without rewiring the first load for continuous operation.

!

WARNING

 

When the selector switch is locked in either the LOAD A or LOAD B 
position, it does not disconnect voltage from the equipment to be serviced.

 

Typical Installations

 

SPDT and DPDT Alternating Relays

 

Figure 2. 

 

Typical Installations for SPDT and DPDT Alternating Relays

 

In the OFF state (Standard Installation), the Control Switch is open, the Alternating Relay is in the 
LOAD A position, and both loads (M1 & M2) are off. When the Control Switch closes, it energizes the 
first load (M1). The red LED marked “LOAD A” glows. As long as the Control Switch remains closed, 
M1 remains energized. When the Control Switch opens, the first load (M1) is turned off and the Alter-
nating Relay toggles to the LOAD B position. When the Control Switch closes again, it energizes the 
second load (M2). The red LED marked “LOAD B” glows. When the Control Switch opens, the second 

Load A: Pi

n

 2

Load B: Pi

n

 8

1

4

I

n

put

Voltage

Co

n

trol

S

witch

L2

L1

3

6

2

7

8

5

1

Load A: Pi

n

s 3 or 11

Load B: Pi

n

s 1 or 9

L2

L1

11

I

n

put

Voltage

Co

n

trol

S

witch

4

8

3

9

6

2

10

7

5

1

Lead

Lag

Load

B

Load

A

L1

L2

8

I

n

put

Voltage

4

3

6

2

7

5

1

Lead

Lag

Load

B

Load

A

L1

L2

8

I

n

put

Voltage

S

top

4

3

6

2

7

5

SPDT

DPDT

DPDT Cross-Wired

DPDT Cross-Wired for 3 Switches

L1

S

PDT

S

PDT

Co

n

trol

S

witch

Co

n

trol

S

witch

O/L

O/L

1

2

8

3

4

5

L1

L2

1

2

3

4

5

Off

M1

M1

M1

M2

L2

M2

M2

8

Standard Installation

Anti-Bounce Installation

Отзывы: