manualshive.com logo in svg
background image

 

IL04906001E

 

Effective 03/07

2

 

IL04906001E

 

Effective 03/07

2

 

load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can 
be repeated again. On relays with DPDT contacts, two pilot lights can be used for remote indication of 
LOAD A or LOAD B status.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along 
with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

 

DPDT Cross-Wired Alternating Relays

 

Figure 3. 

 

Typical Installations for DPDT Cross-Wired Alternating Relays

 

In the OFF state, both the LEAD Control Switch and the LAG Control Switch are open, the Alternating 
Relay is in the LOAD A position, and both loads are off. When the LEAD Control Switch closes, it ener-
gizes the first load (M1). The red LED marked “LOAD A” glows. As long as the LEAD Control Switch 
remains closed, M1 remains energized. If the LAG Control Switch closes, it energizes the second load 
(M2). When the LAG Control Switch opens, the second load (M2) is turned off. When the LEAD Control 
Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B posi-
tion. When the LEAD Control Switch closes, it turns on the second load (M2). The red LED marked 
“LOAD B” glows. If the LAG Control Switch closes, it will energize the first load (M1). When the LAG 
Control Switch opens, the first load (M1) is turned off. When the LEAD Control Switch opens, the sec-
ond load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the pro-
cess can be repeated again.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along 
with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

 

DPDT Cross-Wired for Three-Switch Applications

 

Figure 4. 

 

Typical Installations for DPDT Cross-Wired Relays for Three-Switch Applications

 

In the OFF state, all three switches are open, the Alternating Relay is in the LOAD A position, and both 
loads are off. No action happens with the Alternating Relay or either load when the STOP Switch 
closes. When the LEAD Switch closes, Load #1 (M1) turns on. When the LAG Switch closes, Load #2 
(M2) turns on. Both loads remain on as long as all three switches are closed.
When the LAG Switch opens, Load #2 (M2) remains on because the STOP Switch is still closed. When 
the LEAD Switch opens, Load #1 (M1) remains on because the STOP Switch is still closed. When the 
STOP Switch opens, both Load #1 (M1) and Load #2 (M2) are turned off simultaneously. The Alternat-
ing Relay toggles to the LOAD B position. The entire cycle is then repeated, but with Load #2 (M2) 
energized first followed by Load #1 (M1).
This type of operation is known as “Sequence On – Simultaneously Off (S.O.S.O.)” — the two loads 
are energized sequentially, but remain on together until the STOP switch is opened.
If both the STOP Switch and LEAD Switch fail to close and turn on the first load, both loads will be 
turned on simultaneously when the LAG Switch is closed.

 

Troubleshooting

 

If the unit fails to operate properly, check that all connections are correct per the appropriate wiring 
diagram. If problems continue, contact EATON TRC 1-800-809-2772 for assistance. 

L1

Lag

Lead

Lag

Off

Lead

Cross-Wired

O/L

O/L

1

2

8

3

7

6

L2

L2

L1

M1

Cross-Wired

M2

1

2

3

7

6

M1

M1

M2

M2

8

Standard Installation

Anti-Bounce Installation

L1

Motor

1

Motor

2

L2

L3

L1

M1

M1

M1

M2

M2

M2

M2

M1

L2

L1

Lag

S

witch

Lead

S

witch

S

top

S

witch

L2

L3

1

2

4

8

7

3

6

O/L

O/L

 

load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can 
be repeated again. On relays with DPDT contacts, two pilot lights can be used for remote indication of 
LOAD A or LOAD B status.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along 
with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

 

DPDT Cross-Wired Alternating Relays

 

Figure 3. 

 

Typical Installations for DPDT Cross-Wired Alternating Relays

 

In the OFF state, both the LEAD Control Switch and the LAG Control Switch are open, the Alternating 
Relay is in the LOAD A position, and both loads are off. When the LEAD Control Switch closes, it ener-
gizes the first load (M1). The red LED marked “LOAD A” glows. As long as the LEAD Control Switch 
remains closed, M1 remains energized. If the LAG Control Switch closes, it energizes the second load 
(M2). When the LAG Control Switch opens, the second load (M2) is turned off. When the LEAD Control 
Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B posi-
tion. When the LEAD Control Switch closes, it turns on the second load (M2). The red LED marked 
“LOAD B” glows. If the LAG Control Switch closes, it will energize the first load (M1). When the LAG 
Control Switch opens, the first load (M1) is turned off. When the LEAD Control Switch opens, the sec-
ond load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the pro-
cess can be repeated again.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along 
with two auxiliary contacts is recommended as shown in the Anti-Bounce Installation.

 

DPDT Cross-Wired for Three-Switch Applications

 

Figure 4. 

 

Typical Installations for DPDT Cross-Wired Relays for Three-Switch Applications

 

In the OFF state, all three switches are open, the Alternating Relay is in the LOAD A position, and both 
loads are off. No action happens with the Alternating Relay or either load when the STOP Switch 
closes. When the LEAD Switch closes, Load #1 (M1) turns on. When the LAG Switch closes, Load #2 
(M2) turns on. Both loads remain on as long as all three switches are closed.
When the LAG Switch opens, Load #2 (M2) remains on because the STOP Switch is still closed. When 
the LEAD Switch opens, Load #1 (M1) remains on because the STOP Switch is still closed. When the 
STOP Switch opens, both Load #1 (M1) and Load #2 (M2) are turned off simultaneously. The Alternat-
ing Relay toggles to the LOAD B position. The entire cycle is then repeated, but with Load #2 (M2) 
energized first followed by Load #1 (M1).
This type of operation is known as “Sequence On – Simultaneously Off (S.O.S.O.)” — the two loads 
are energized sequentially, but remain on together until the STOP switch is opened.
If both the STOP Switch and LEAD Switch fail to close and turn on the first load, both loads will be 
turned on simultaneously when the LAG Switch is closed.

 

Troubleshooting

 

If the unit fails to operate properly, check that all connections are correct per the appropriate wiring 
diagram. If problems continue, contact EATON TRC 1-800-809-2772 for assistance. 

L1

Lag

Lead

Lag

Off

Lead

Cross-Wired

O/L

O/L

1

2

8

3

7

6

L2

L2

L1

M1

Cross-Wired

M2

1

2

3

7

6

M1

M1

M2

M2

8

Standard Installation

Anti-Bounce Installation

L1

Motor

1

Motor

2

L2

L3

L1

M1

M1

M1

M2

M2

M2

M2

M1

L2

L1

Lag

S

witch

Lead

S

witch

S

top

S

witch

L2

L3

1

2

4

8

7

3

6

O/L

O/L

Отзывы: