4-4 Protection
and
Control
BE1-CDS220
D3
D2
D1
D0
AUTO
SG3
SG2
SG1
SG0
SGC
D2647-20
08-21-98
Figure 4-3. Input Control Mode 1
When the setting group control function block is enabled for Mode 2, inputs D0 and D1 are read as binary
encoded (Table 4-2). Inputs D2 and D3 are ignored. A new coded input must be stable for approximately
1 second for the setting group change to occur. After a setting group change occurs, no setting group
change can occur within two times the SGC alarm on time.
Table 4-2. Setting Group Binary Codes
Binary Code
D1 D0
Decimal Equivalent
Setting Group
0 0 0
SG0
0 1 1
SG1
1 0 2
SG2
1 1 3
SG3
When using control Mode 2, the active setting group is controlled by a binary signal applied to discrete
inputs D0 and D1. This requires separate logic equations for only D0 and D1 if all setting groups are to be
used. Figure 4-4 shows how the active setting group follows the binary sum of the D0 and D1 inputs
except when blocked by the AUTO input. Note that a pulse on the D1 input while D0 is also active does
not initiate a setting change to SG3 because the AUTO input is active.
D2647-21
08-21-98
D3
D2
D1
D0
AUTO
SG3
SG2
SG1
SG0
SGC
Figure 4-4. Input Control Mode 2
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......