background image

 

ABB Automation Inc.

Substation Automation and Protection Division
Coral Springs, FL 33065

Instruction Leaflet

 

All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is desired
by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB
Power T&D Company Inc.  representative should be contacted.

Effective:

December 1999

( | ) Denotes Change Since Previous Issue

Printed in U.S.A

.

ABB

ABB

ABB

ABB

41-971.3M

Type HCB-1
Pilot-wire Relay System

Supersedes I.L. 41-971.3L, Dated August 1996

!

CAUTION

Before putting protective relays into service,

remove all blocking which may have been

inserted for the purpose of securing the parts

during shipment, make sure that all moving

parts operate freely, inspect the contacts to

see that they are clean and close properly, and

operate the relay to check the settings and

electrical connections.

1.0 APPLICATION

The type HCB-1 relay is a high speed pilot-wire relay
designed for the complete phase and ground protec-
tion of two and three terminal transmission lines.
Simultaneous tripping of the relay at each terminal is
obtained in about 20 milliseconds for all faults. A
complete installation for a two terminal line consists
of two relays, two insulating transformers, and an
interconnecting pilot-wire circuit. For a three terminal
line, three relays, three insulating transformers, and a
wye-connected pilot-wire circuit with branches of
equal series resistance are required.

The HCB-1 and HCB relays are not compatible, since
the filter response is not the same.

2.0 CONSTRUCTION

The relay consists of a combination positive, nega-
tive, and zero phase sequence filter, a saturating aux-

iliary transformer, two full wave rectifier units, a polar
unit, a Zener clipper, and an indicating contactor
switch (ICS), all mounted in a single case. The exter-
nal equipment normally supplied with the relay con-
sists of an insulating transformer, a millimeter and
test switch.

2.1.

SEQUENCE FILTER

The sequence filter consists of a three-legged iron
core reactor and a set of resistors designated R

1

 and

R

0

. The reactor has three windings; two primary and

a tapped secondary winding, wound on the center leg
of a “F” type of lamination. The secondary taps are
wired to the A, B and C tap connections in front of the
relay. R

0

 consists of three tube resistors with taps

wired to the F, G and H tap connections in the front of
the relay.

2.2.

SATURATING TRANSFORMER

The output of the sequence filter connects to the pri-
mary of a two-winding saturating transformer. The pri-
mary winding is tapped and wired to a tap block T in
the front of the relay. The secondary winding is con-
nected to the Zener clipper circuit and from a fixed
tap to the relay coil circuits.

2.3.

POLAR UNIT

This unit consists of a rectangular-shape magnetic
frame, an electromagnet, a permanent magnet, and
an armature with either one or two contacts. The
poles of the crescent-shaped permanent magnet
bridge the magnetic frame. The magnetic frame con-
sists of three pieces joined in the rear with two brass
rods and silver solder. These non-magnetic joints

R

Содержание HCB-1

Страница 1: ... and a wye connected pilot wire circuit with branches of equal series resistance are required The HCB 1 and HCB relays are not compatible since the filter response is not the same 2 0 CONSTRUCTION The relay consists of a combination positive nega tive and zero phase sequence filter a saturating aux iliary transformer two full wave rectifier units a polar unit a Zener clipper and an indicating cont...

Страница 2: ...41 971 3M Type HCB 1 Pilot Wire Relay System 2 Figure 1 Type HCB 1 Relay Without Case Front View ...

Страница 3: ...Type HCB 1 Pilot Wire Relay System 41 971 3M 3 Figure 2 Type HCB 1 Relay Without Case Rear View ...

Страница 4: ...put VF of a magnitude which is a function of the positive negative and zero sequence components of fault current This voltage VF is impressed on the primary wiring of the saturating transformer The saturating transformer output volt age VS is impressed on the primary wiring of the saturating transformer The saturating transformer output voltage VS is impressed on the primary wir ing of the saturat...

Страница 5: ... plus the magnetic restraint or bias expressed in ampere turns 4 0 CHARACTERISTICS The voltage VF impressed by the filter upon the sat urating transformer varies with the tap setting A B C of the relay The sequence network in the relay is arranged for several possible combinations of sequence compo nents For tap C the output of the network will contain the positive negative and zero sequence compo...

Страница 6: ... is Equ 2 4 1 SINGLE RELAY PICKUP Pilot wire Open IS Single relay pickup IS is defined as the phase cur rent required to operate one relay with the pilot wire side of the insulating transformer open circuited H1 H4 The single relay pickup point in terms of filter voltage is Equ 3 where T is the saturating transformer tap value Sin gle relay pickup is defined by equating 2 and 3 Equ 4 Current IS va...

Страница 7: ...pilot wire shunt capacitance the relays will operate at their nominal pickup point The minimum trip points will vary somewhat from nominal value depending on the pilot wire constants and the magnitude and phase angle of the various relay input currents For example Figure 6 shows the relay operating points for a two terminal line assuming input current one relay only An example of the characteristi...

Страница 8: ...mpressed across either insulating trans former H1 H4 Terminals as a result of induction or a Table 4 Insulating Transformer Rate No of Relays 4 1 6 1 RL CS RL CS 2 2000 1 5 4500 0 33 3 500 LEG 1 8 1000 LEG 0 75 rise in station ground potential should be less than 7 5 volts to prevent undesired relay operation For three terminal applications the loop resistance of all legs of the pilot wire must be...

Страница 9: ... the seal in contacts of the indicat ing contactor switch will safely carry this current long enough to trip a circuit breaker The indicating contactor switch has two taps that pro vide a pick up setting of 0 2 or 2 amperes To change taps requires connecting the lead located in front of the tap block to the desired setting by means of a screw connection 5 0 SETTINGS There are four settings in the ...

Страница 10: ...vely 5 2 1 Phase Fault Sensitivity R1 and Taps The phase fault pickup is determined by the B C and T taps In order to operate on the minimum 3 phase fault current the T tap should be set for not more than Equ 8 In order to prevent operation on load current if the pilot wires become open circuited the T tap should be set for not less than Equ 9 The available taps are T 4 5 6 7 8 10 12 Where suffici...

Страница 11: ...tap and maximum restraint In most applications it is not necessary to recalibrate the relay when changing to the minimum restraint tap 5 2 4 Tapped Loads Where one transformer bank is tapped to a line pro tected with two HCB 1 relays the critical point is to set above the fault current flow for a fault on the other side of the bank Set the T for not less than Equ 11 where IPL total secondary fault...

Страница 12: ... the relay is performed The HCB 1 is factory calibrated at the following taps R1 C Tap R0 H Tap T 4 Amps If other tap settings are used the HCB 1 relay must be recalibrated at the applied settings to obtain pickup current within 5 of the I L specifications 7 1 MAIN UNIT Connect the relay to the insulating transformer as shown in Figure 8 and set C H 4 and maximum restraint tap With the insulating ...

Страница 13: ... Over all calibration can be checked by the procedure described under Acceptance Tests If the relay has been recalibrated in the minimum restraint tap fac tory calibration is made in the maximum restraint tap the RPW test should be made in accordance with Table 6 instead of Table 5 7 2 2 Sequence Filter Remove tap screw from upper tap plate and connect a high resistance voltmeter across the common...

Страница 14: ...or maximum restraint IO 0 16IR 4 7 3 CALIBRATION PROCEDURE If the factory calibration has been disturbed the fol lowing procedure should be followed to recalibrate the relay 7 3 1 Filter Calibration This adjustment is performed by means of the taps on the formed wire resistor see Figure 2 for loca tion 1 Remove tap screw from upper tap plate and set lower tap screws in A and H 2 Connect voltmeter ...

Страница 15: ...w remove the short from H1 to H4 and check pickup for I79 If value has changed from before it will be necessary to re adjust the right hand shunt Sev eral trials may be necessary before the relay will pickup at 2 10 amperes and dropout at 1 0 amperes or higher In each case 40 amperes should be applied to terminal 5 and 3 with the H1 and H4 termi nals shorted before any additional adjustments are p...

Страница 16: ...ble test should be set up using a low resistance ac milliammeter 2 Red handle flexitest case switch should be open to interrupt the breaker trip circuit 3 A test crew is necessary at each substation with a means of communication between them 4 When the test calls for delivering only specified currents to the relay it is necessary to use a thin piece of insulating material in the ammeter test jack ...

Страница 17: ...REQUIREMENTS The volt ampere burden of the type HCB 1 relay is practically independent of the pilot wire resistance and of the current tap used The following burdens were measured at a balanced three phase current of 5 amperes The angles above are the degrees by which the current lags is respective voltage The continuous rating of the relay is 10 amperes The two second overload ratings of the rela...

Страница 18: ... to Tap 20 to 30 ohms Start to Finish 110 to 140 Ohms Polar Unit Operating Coil 290 320 Polar Unit Restraining Coil Maximum 12 16 ohms Minimum 9 12 ohms Resistor RC 41 44 ohms Tube Resistor R0 Total of 1 6 ohms Formed Resistor R1 0 131 ohms Rectifiers IN91 Germanium Diodes Indicating Contactor Switch 0 2 amp Tap 6 5 ohms 2 0 amp Tap o 15 ohms ...

Страница 19: ...Type HCB 1 Pilot Wire Relay System 41 971 3M 19 THIS SPACE RESERVED FOR NOTES ...

Страница 20: ...41 971 3M Type HCB 1 Pilot Wire Relay System 20 Figure 9 HCB 1 Relay System Verification Tests ...

Страница 21: ...Type HCB 1 Pilot Wire Relay System 41 971 3M 21 ...

Страница 22: ...41 971 3M Type HCB 1 Pilot Wire Relay System 22 Figure 10 Typical HCB 1 Relay System ...

Страница 23: ...Type HCB 1 Pilot Wire Relay System 41 971 3M 23 Sub 15 4810D98 ...

Страница 24: ...cal Test Output vs Relay Current in a Two Terminal Line with 2000 Ohm Pilot Wire Resistance with or without 10 mfd Capacitor Figure 13 Typical Curve of Relay Output vs Positive Se quence Input Test Switch in Local Position Figure 14 Outline and Drilling Plan of S 290B664G65 Balancing Resistor for Three Terminal Line Application Sub 1 538103 Sub 1 538101 Sub 1 880A797 Sub 1 538102 ...

Страница 25: ...ilot Wire Relay System 41 971 3M 25 Figure 15 Outline and Drilling Plan of HCB 1 Relay Insulating Transformer Figure 16 Outline and Drilling Plan of the Semi Flush Type Test Milliammeter Sub 1 184A739 Sub 2 13C5342 ...

Страница 26: ...1 971 3M Type HCB 1 Pilot Wire Relay System 26 Figure 17 Outline of the Test Milliammeter Auxiliary Transformer Figure 18 Outline and Drilling Plan of the Type W 2 Test Switch Sub 1 293B226 5D1523 Sub 2 ...

Страница 27: ...Type HCB 1 Pilot Wire Relay System 41 971 3M 27 THIS PAGE RESERVED FOR NOTES ...

Страница 28: ...57D7905 Printed in U S A ABB Automation Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 ABB visit our website at www abbus com papd Figure 19 Outline and Drilling Plan for t he Type HCB 1 Relay in the Type FT 42 Case ...

Отзывы: