13-44
Testing And Maintenance
BE1-CDS220
Step 1.
Parallel a 60 Hz current source and a second 300 Hz current source to terminals B1, B2
(A-phase, input 1). Same as Figure 13-14 except for the applied harmonic frequency.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2.
Send the commands listed in Table 13-30 to the relay to setup a test of the pickup of the fifth
harmonic restraint elements.
Table 13-30. Fifth Harmonic Restraint Elements Setup Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm
overwrite
SL-N=5HAR
Sets 5HAR as custom logic name
SL-87=1,0 Enables
87
SL-VO1=87RT
Enables OUT1 to close with 87 restrained trip
SL-VO2=5THHAR
Enables OUT2 to close when 5
th
harmonic restrains
87RT
SG-CT1=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87RT,87RPU,0
Enable 87RT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
#-87=0.35,15,0,35,0,1
Minpu = 0.35, slope = 15%, 2
nd
= disabled, 5
th
= 35%,
URO = disabled, 2
nd
harm sharing = shared
E Exit
Y Save
settings
Step 3.
Apply 2.0 amps of 60 Hz current to the A-phase input 1. The OUT1 (87RT restrained trip)
output contact should close upon application of current.
Step 4.
Apply 300 Hz current on the source paralleled to A-phase input 1 and slowly increase the
current from zero until OUT2 closes (and conversely, OUT1 opens).
Step 5.
Record the current magnitude from Step 4 that caused OUT 2 to close and OUT1 to open.
These output contact changes indicated that the 5
th
harmonic restraint function is now
restraining the 87RT operation.
Step 6.
Remove both 60 Hz and 300 Hz currents.
Step 7.
To arrive at a 5
th
harmonic inhibit percentage value, divide the magnitude of the applied 5
th
harmonic current (300 Hz) by the magnitude of the applied 60 Hz input current. For this
particular test, this value should be equal to 0.70 amperes @ 300 Hz
÷
2 A @ 60 Hz = 35 %.
Verify that the 5
th
harmonic inhibit function restrains operation at the expected value based on
settings from Step 2.
Step 8.
(Optional) Repeat steps 2 through 7 for phases B and C.
Step 9.
(Optional) Repeat Steps 2 through 8 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
Unrestrained Pickup Verification
Purpose:
To verify the accuracy of the unrestrained operation of the 87 element.
Reference Commands:
SL-87, SL- VO, SG-CT, S(n)-87, S(n)-TAP87
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......