13-56
Testing And Maintenance
BE1-CDS220
Using the basic information in Table 13-45, program the pickup of the elements for setting
group 1 and, optionally, proceed with the testing.
Timing Verification (51/151/251)
Purpose:
To verify the accuracy of the timing operation of the 51/151/251 elements.
Reference Commands:
SL-51/151/251, S<n>-51
Step 1.
Connect a current source to terminals B1 and B2 (A-phase input 1).
Step 2.
To initially prepare the 51/151/251 elements for testing, send the commands in Table 13-50 to
the relay.
Table 13-50. 51/151/251 Overcurrent Timing Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm
overwrite
SL-N= 51
Name custom logic for this test
SL-51=1,0
Enables 51P/51N/51Q, CT input 1
SL-VO1=51PT
Enables OUT1 to close for 50P trip
SL-VO2=51NT
Enables OUT2 to close for 51N trip
SL-VO3=51QT
Enables OUT3 to close for 51Q trip
SG-CT1=1,WYE,NA,0
Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=51PT+
51NT+51QT,51PPU+
51NPU+51QPU,0
Enable 51PT+51NT+51QT to log targets and
trigger fault recording
E Exit
Y Save
settings
Step 3.
Transmit to the relay the appropriate row of the setting commands S0-51P from Table 13-51. If
your relay is supplied with the HMI option, you may also go to the front panel interface screen
\PROT\SG0\50T\50T and edit the 51P, 51N, and 51Q settings.
Table 13-51. Time Overcurrent 51 Element Test Settings
Sensing
Input Type
Phase Neutral
Negative
Sequence
1 A
S0-51P=1.0,0.5,I2
S0-51N=1.0,0.5,I2 S0-51QN=0.33,0.5,I2
5 A
S0-51P=5.0,0.5,I2
S0-51N=5.0,0.5,I2 S0-51QN=1.67,0.5,I2
Notes for Table 13-51
1. See Sidebar 13-10 for more information on negative sequence pickup.
Step 4.
Using the values listed in Table 13-52, apply the current listed to the A phase current input and
measure the time between the application of current and the time it takes for the relay outputs
OUT1, OUT2, and OUT3 to close. Verify that the relay performs with the specified limits. An
ohm-meter or continuity tester may be used to monitor the output contacts status.
Step 5.
After each pickup occurs, slowly ramp current down until OUT1, OUT2, and OUT3 open.
Dropout should occur at 95%
±
2%.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......