BE1-CDS220 Installation
12-21
P0001-07
08-11-00
AØ
BØ
CØ
BUS SOURCE
BREAKER
High speed bus differential zone. Source current IN equals the radial load current OUT.
Phase, Residual, and
I
2
overcurrent elements can be connected to either CT circuit for backup protectiion. For more
information on applying overcurrent backup, refer to Section 8, Application.
For complete metering and independent backup protection, use a BE1-951 Overcurrent Protection System with the
BE1-CDS220. A BE1-951 on the Bus Source Breaker can also be used in conjunction with Feeder BE1-851 or
BE1-951 relays to create a high speed bus interlocking protection scheme. To add only metering to the BE1-
CDS220, connect a BE1-MMS100.
1
2
4
1
BE1-CDS220
B2
B5
B1
B3
B6
B4
I
C1
I
B1
I
A1
3
B10
B14
B12
B9
I
A2
I
B2
I
C2
B13
B11
52
52
52
2
2
3
1
RADIAL LOAD
RADIAL LOAD
RADIAL LOAD
Overcurrent neutral ground (
I
N
) operates on internally calculated residual (3I0) current.
3
52
BUS TIE
BREAKER
Figure 12-24. BE1-CDS220 Connected for Low-Impedance Bus Differential Protection
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......