BE1-CDS220 Application
8-39
Function
Purpose
BESTlogic
Expression
Mode Setting
50TP
Applied to bus main (CT 1). Normally for fast bus OC protection (2-4
cycle delay) as backup to 87. When in feeder relay backup mode,
provides near instantaneous for feeder. Block when feeder relay is
picked up indicating that the fault is on a feeder.
IN5
1 (CT Input 1)
50TN
Applied to bus main (CT 1). Normally for fast bus OC protection (2-4
cycle delay) as backup to 87. When in feeder relay backup mode,
provides near instantaneous for feeder. Block when feeder relay is
picked up indicating that the fault is on a feeder.
IN5
1 (CT Input 1)
50TQ
Applied to bus main (CT 1). Normally for fast bus OC protection (2-4
cycle delay) as backup to 87. When in feeder relay backup mode,
provides near instantaneous for feeder. Block when feeder relay is
picked up indicating that the fault is on a feeder.
IN5
1 (CT Input 1)
150TP
Applied to bus main (CT 1). Used for backup bus OC trip. 18-20
cycles delay (no feeder picked up interlock). Provides primary OC
protection when 50T elements are used for feeder relay backup.
0
1 (CT Input 1)
150TN
Applied to bus main (CT 1). Used for backup bus OC trip. 18-20
cycles delay (no feeder picked up interlock). Provides primary OC
protection when 50T elements are used for feeder relay backup.
0
1 (CT Input 1)
150TQ
Applied to bus main (CT 1). Used for backup bus OC trip. 18-20
cycles delay (no feeder picked up interlock). Provides primary OC
protection when 50T elements are used for feeder relay backup.
0
1 (CT Input 1)
GROUP
Auto/Manual Logic: Switch to setting group 1 if feeder relay is out of
service as indicated by closed contact from relay with BACKUP logic
such as BE1-851, BE1-951, or BE1-CDS220.
IN7
2 (Binary Inputs)
Table 8-24. BUS-W-BU Virtual Switch Logic
State Labels
Switch
Purpose Mode
Label
Closed Open
43
Used as differential cutoff. The 87 is blocked
when the switch is in the closed state.
2 (On/Off)
87-CUTOFF
DISABLD
NORMAL
743
Selects test mode so that reclosing and BF are
disabled when virtual switch is closed.
2 (On/Off)
TEST-
MODE-
TSTMODE
NORMAL
101
Allows breaker to be tripped or closed manually
from HMI or ASCII command interface
1 (Enabled)
N/A
N/A
N/A
Table 8-25. BUS-W-BU Output Logic
State Labels
Output
Purpose Description
Label
True False
VOA
Relay Trouble alarm.
OUTA contact closes when relay
trouble alarm occurs.
RELAY-TROU
ACTIVE
NORMAL
BESTlogic Expression: VOA=0
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......