BE1-CDS220 Application
8-51
CKTMON
CIRCUIT
MONITOR
TESTMODE ENABLE
SWITCH
1=NORMAL 0=ENABLED
+
-
IN4
343
1=ENABLED 0=NORMAL
VIRTUAL SWITCH
TESTMODE ENABLE
VO4
BLOCK UPSTREAM
INSTANTANEOUS
VO12
PROTECTION PICKED
UP EXPRESSION
INITIATE EXPRESSION
BREAKER FAILURE
VO10
INI
BLK
BFPU
BFT
BF
VO5
BREAKER
FAILURE
TRIP
10-27-99
D2857-15.vsd
Figure 8-16. Trip Circuit Continuity and Voltage Monitor
Close-Circuit Monitor
A close-circuit monitor is not included in any of the preprogrammed logic schemes. This function may be
added by using a 62 function block and a contact sensing input (INX) to monitor the close circuit. The logic
is shown in Figure 8-17. The output of the 62 protection block will close the designated output contact
(VOY) when an open breaker and an open close-circuit condition exists. The S<g>-62 command is used
to provide a 500 millisecond time delay to inhibit the momentary alarm that will occur due to the timing
difference between the two signals.
VOX
INI
BLK
IN1
(52B)
INX
(CLOSE CKT)
62 TIMER
PICKUP
TIME
DROPOUT
TIME
D
2
5
8
7
-0
2
3-13-97
0=BREAKER CLOSED
1=BREAKER OPEN
0=CLOSE CKT OPEN
1=CLOSE CKT OK
62
VOY
VOX=IN1*/INX
SL-62=1,VOX
S<g>-62=500,0
SL-VOY=62
Figure 8-17. Close Circuit Monitor Logic
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......