CPR 126-1C 

CURRENT PROTECTION RELAY

TECHNICAL SPECIFICATION

MECHANICAL INSTALLATION

TERMINAL CONNECTION

FEATURES:

INPUT SPECIFICATION:

DISPLAY AND KEY:

OUTPUT SPECIFICATION:

AUXILIARY SUPPLY:

GENERAL SPECIFICATION:

Primary CT value

True RMS Measurement

Protection available

Over Load

Auto/Manual /ZVR (Zero Value Reset) reset option

Under Load

3 digit bright LED display

Three phase current display with LED indication

Auto save out feature

Time parameter : Power on delay
                              Trip delay
                              Initial time delay
                              Recovery time (Auto reset)

Secondary current AC

Resolution

5 to 999 Selectable

0.5 to 5 Amp AC

0.01A, 0.1A,  1A

Display

Relay

Supply voltage

Dimension (mm) 

Keys

Relay Type

Power consumption
(VA RATING)

Rating

Trip Setting

Time parameter

3 digit, 1line, 7 seg, 0.4” RED LED

1 nos.

75 (H) x 45 (W) x 110 (D) mm

SET, INC, DEC/ RST

1  C/O (NO-C-NC)

3 VA @ 230V AC MAX

10A, 230V AC/28 V DC

Under current : 0.00 to 100% of
primary C.T value

Trip delay time : 0 to 999 sec
Power on time : 0 to 99 sec
Initial time delay : 0 to 99 sec 

Over current : 0.00 - 125% of
primary C.T value

ENVIRONMENT CONDITION:

Relative Humidity

 Operating Temp.

0°C to 55°C

UP to 95% RH 
(non-condensing)

100 to 270V AC, 50-60Hz

Recovery time : 0 to 99 sec

110

Front View(mm)

A

SET

NO

L

N

C NC

CPR 126-1C

R

4 0 0

75

Side View(mm)

75

45

NO

L

N

C NC

CPR 126-1C

R

A

SET

L1

L2

L3

N

TO

LOAD

Class 1.0 (Standard)

ACCURACY

Page -1