Single-Phase Solid State Relay
HSR-2
Thank you for purchasing Hanyoung Nux products. Please read the instruction
manual carefully before using this product, and use the product correctly.
Also, please keep this instruction manual where you can view it any time.
INSTRUCTION MANUAL
▍
Safety information
Please read the safety information carefully before the use, and use the product correctly.
The alerts declared in the manual are classified into
Danger
and
Warning
according to their importance.
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or
properties damage
DANGER
WARNING
CAUTION
• Please read the safety information carefully before the use,
and use the product correctly.
• If there is a possibility that a malfunction or abnormality of
this product may lead to a serious accident, install an
appropriate protection circuit on the outside and plan to
prevent accidents.
• Please supply the rated power voltage, in order to prevent
product breakdowns or malfunctions.
• To prevent electric shocks and malfunctions, do not supply
power until the wiring is completed.
• Please disassemble the product after turning OFF the power.
• Any use of the product other than those specified by the
manufacturer may result in personal injury or property damage.
• Please use this product after installing it to a panel,
because there is a risk of electric shock.
• 4 - 32 V d.c model signal inputs must be supplied with
an isolated and limited voltage/current or Class2,
SELV power supply.
• Short circuit rated current is 3kA.
• Please make sure that the product specifications are the same as you ordered.
• Please use the product in places where corrosive gases
(especially harmful gases, ammonia, etc.) and flammable
gases are not generated.
• Please use the product in places without liquids, oils,
chemicals, steam, dust, salt, iron, etc. (pollution degree 1 or 2).
• Please avoid places where large inductive interference, static
electricity,magnetic noise are generated.
• Please avoid places with heat accumulation caused by direct
sunlight, radiant heat, etc.
• When water enters, short circuit or fire may occur, so please
inspect the product carefully.
• Do not connect anything to the unused terminals.
• For DC types, please wire correctly,
after checking the polarity of the terminals.
• When disposing of the product, treat it as industrial waste.
• Since a heat sink corner is sharp, it would lead to a serious injury.
• When electricity flows, desktop or heat sink's corner temperature
would be high so that it could lead people to suffer burns.
• When it is out of order, please separate HSR from head sink and
change only HSR.
• This model has epoxy molding for the purpose of safety,
reliability and extends of the life.
• When applying an electric current, HSR is heated more and more.
So, it has more durable at low heat sink temperature and
ambient temperature.
• Note 1) The N option model must be installed and used with a
heatsink (HSN or HSM series, sold separately) of our company's
appropriate specifications.
However). When using a separate heat sink, it is recommended to
select and install the heat sink size based on the thermal
resistance value (Note 1).
• The input/output terminals are subject to electric shock risk.
Never let the input/output terminals come in contact
with your body or conductive substances.
DANGER
CAUTION
WARNING
MC0801KE231018
▍Suffix code
Model
Low
HSR-2D10LZ□ HSR-2D20LZ□ HSR-2D30LZ□ HSR-2D40LZ□ HSR-2D50LZ□ HSR-2D70LZ□
HSR-2D10LR□ HSR-2D20LR□ HSR-2D30LR□ HSR-2D40LR□ HSR-2D50LR□ HSR-2D70LR□
High
HSR-2D10HZ□ HSR-2D20HZ□ HSR-2D30HZ□ HSR-2D40HZ□ HSR-2D50HZ□ HSR-2D70HZ□
HSR-2D10HR□ HSR-2D20HR□ HSR-2D30HR□ HSR-2D40HR□ HSR-2D50HR□ HSR-2D70HR□
L
O
A
D
Rated Load
Voltage
Low
24 - 240 V a.c. 50/60 Hz
High
24 - 480 V a.c. 50/60 Hz
Peak Voltage
(Non-repetition)
Low
1,200V
High
Rated load current
10A
20A
30A
40A
50A
70A
Surge current 60Hz
(8.3ms No repetition)
Low
170A
260A
420A
525A
High
170A
250A
370A
525A
Surge current 50Hz
(10ms No repetition)
Low
160A
250A
400A
500A
High
160A
240A
340A
500A
Leakage current
Less than 20 mA
Output ON voltage dropping
Less than 1.6 V (R.M.S)
I
N
P
U
T
Rated Voltage
5 - 24 V d.c.
Operating Voltage Range
(ON Voltage)
4 - 32 V d.c.
return voltage (OFF Voltage)
Less than 3 V
Impedance
Less than 4 kΩ
Current Consumption
Constant current method: 14 mA or less
Response Time
1/2 Cycle + 1 ms max. (“R”type below 1ms)
Insulating Resistance
500 V d.c., 100 MΩ (Between input and output and case)
Dielectric strength
2,500 V a.c. (For 1min at 60㎐)
Rated impulse withstand voltage
(Uimp)
2,500 V
Vibration resistance
10 - 55 Hz, Double amplitude : 1.5 mm, X-Y-Z each axis direction for 2 hour
Shock resistance
1,000 ㎨, X·Y·Z each axis 3 time
Storage Temperature
-30 ~ 90 ℃
Ambient Temperature & Humidity
-30 ~ 80 ℃ (No Condensation), 45 ~ 85 % RH
Pollution level grade
2level pollution
bolt tightening torque
Input terminal: 0.05 Nm / Output terminal: 0.25 Nm
Usage
Resistive load
Accepted standard
(EN 60947-4-3)
Weight
Approx 110 g
Approx 120 g
█
DC input
Model
Low
HSR-2A10LZ□ HSR-2A20LZ□
HSR-2A30LZ□
HSR-2A40LZ□
HSR-2A50LZ□
HSR-2A70LZ□
HSR-2A10LR□ HSR-2A20LR□
HSR-2A30LR□
HSR-2A40LR□
HSR-2A50LR□
HSR-2A70LR□
High
HSR-2A10HZ□ HSR-2A20HZ□ HSR-2A30HZ□ HSR-2A40HZ□ HSR-2A50HZ□ HSR-2A70HZ□
HSR-2A10HR□ HSR-2A20HR□ HSR-2A30HR□ HSR-2A40HR□ HSR-2A50HR□ HSR-2A70HR□
L
O
A
D
Rated Load
Voltage
Low
24 - 240 V a.c. 50/60Hz
High
24 - 480 V a.c. 50/60Hz
Peak Voltage
(Non-repetition)
Low
1,200V
High
Rated load current
10A
20A
30A
40A
50A
70A
Surge current 60Hz
(8.3ms No repetition)
Low
170A
260A
420A
525A
High
170A
250A
370A
525A
Surge current 50Hz
(10ms No repetition)
Low
160A
250A
400A
500A
High
160A
240A
340A
500A
Leakage current
Less than 20 mA
Output ON voltage dropping
Less than 1.6 V (R.M.S)
I
N
P
U
T
Rated Voltage
100-240 V a.c. 50/60Hz (public)
Operating Voltage Range
(ON Voltage)
90-264 V a.c. 50/60Hz (public)
return voltage (OFF Voltage)
Less than 50 V
Impedance
Less than 40 kΩ
Current Consumption
Less than 14 mA
Response Time
1/2 Cycle + 1 ms max. (“R”type below 1ms)
Insulating Resistance
500 V d.c., 100 MΩ (Between input and output and case)
Dielectric strength
2,500 V a.c. (For 1min at 60㎐)
Rated impulse withstand voltage
(Uimp)
2,500 V
Vibration resistance
10 - 55 Hz, Double amplitude : 1.5 mm, X-Y-Z each axis direction for 2 hour
Shock resistance
1,000 ㎨, X·Y·Z each axis 3 time
Storage Temperature
-30 ~ 90 ℃
Ambient Temperature & Humidity
-30 ~ 80 ℃ (No Condensation), 45 ~ 85 % RH
Pollution level grade
2 level pollution
bolt tightening torque
Input terminal: 0.05 Nm / Output terminal: 0.25 Nm
Usage
Resistive load
Accepted standard
(EN 60947-4-3)
Weight
Approx 110 g
Approx 120 g
█
AC input
▍Dimensions
[ Unit : ㎜ ]
▍Equivalent Circuit
※
This model does not have a fuse internally. So we suggest using
fast-acting fuse separately on the outside as following picture.
(using gG/gL type fuse according to IEC 60269 standard)
5-24Vd.c.
100-240Va.c.
Load voltage
Load
Load voltage
Load
Voltage output of
temperature controller, PLC etc.
▍Connection
5-24Vd.c.
100-240Va.c.
Load voltage
Load
Load voltage
Load
Voltage output of
temperature controller, PLC etc.
• Please make intervals more than the sizes in the following picture.
• Please install wiring duct less than half the height of the heat sink
to prevent the flow of air.
• It is good to use Hanyoung Nux's HSR in lower than ambient
temperature 40 ℃ so, please use it lower than standard temperature.
• When installing the HSR, be sure to installthe heat sink in the
vertical direction.
• Unavoidably, if installed horizontally, theperformance of the
product will drop below 50 %
▍Installation
• Using standard heat sink is mandatory for this product.
• Even the standard heat sink is used, HSR damage may occur if the environment temperature
rises or if the ventilation does not work well. (Environment temperature : over 40 ℃)
• The normal HSR element is damaged at the maximum temperature of 125 ℃ . When the
temperature of heat sink is 85° C, the temperature of the element reaches around 125 ℃ .
Therefore, during operation, measure the temperature of heat sink.
• When you connect HSR onto the heat sink, heat-transmitting grease is needed for smooth heat transmission.
• To prevent separation by vibration, tighten up with bolts.
• Do not use any insulating materials such as wood, plastic or rubber.
The standard heat sink must be greased on the bottom side as shown and connected.
※ The heatproof silicon grease must be applied thoroughly on the heat sink as well as the bottom of HSR.
The case side of heat sink needs to be installed on up and down directions.
▍Precautions during the use of Heat Sink
█ HSR-2D
█ HSR-2A
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hanyoungnux.com
HANYOUNGNUX CO.,LTD
64.0
42.0
4.4
48.0
R2.2
Ø4.4
27.3
4.0
42.16
64.35
Ă4.4
R2.2
48.0
4.4
31.8
4.0
64.0
42.0
4.4
48.0
R2.2
Ø4.4
27.3
4.0
42.16
64.35
Ă4.4
R2.2
48.0
4.4
31.8
4.0
64.0
42.0
4.4
48.0
R2.2
Ø4.4
27.3
4.0
42.16
64.35
Ă4.4
R2.2
48.0
4.4
31.8
4.0
█ HSM series
▍Heat Sink
60.0
L
4.
5
130.0
139.0
2-M4
5.
0
99.0
48.
5
99.0
5.0
█ HSN series
▍Input/Loder
Ambient Temperature(℃)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Ambient Temperature(℃)
Ambient Temperature(℃)
HSR-2□55
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□20/25
HSR-2□10
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□40
HSR-2□30
10
10
20
30
40
50
55
60
70
20
30
40
50
60
70
80
90
0
HSR-2□70
HSR-2□50
Ambient Temperature(℃)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Ambient Temperature(℃)
Ambient Temperature(℃)
HSR-2□55
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□20/25
HSR-2□10
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□40
HSR-2□30
10
10
20
30
40
50
55
60
70
20
30
40
50
60
70
80
90
0
HSR-2□70
HSR-2□50
Ambient Temperature(℃)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Lo
ad C
urr
ent (A)
Ambient Temperature(℃)
Ambient Temperature(℃)
HSR-2□55
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□20/25
HSR-2□10
10
10
15
20
25
30
35
40
20
30
40
50
60
70
80
90
0
HSR-2□40
HSR-2□30
10
10
20
30
40
50
55
60
70
20
30
40
50
60
70
80
90
0
HSR-2□70
HSR-2□50
▍Specifications
Model
Code
Information
HSR-2
□ □ □ □ □
Single-Phase Solid State Relay
Control
Input Voltage D
4 - 32 V d.c.
A
90 - 240 V a.c.
Rated load current
10
10A
20
20A
30
30A
40
40A
50
50A
70
70A
Rated load voltage
L
24 - 240 V a.c.
(Low voltage)
H
24 - 480 V a.c.
(High voltage)
Operation method
(Switching Mode)
Z
Zero Cross Switching (Standard product)
R
Random Switching
Heatsink option
T Heat sink + bimetal mounting (50 A, 70 A only)
N No Heat sink
※CAUTION 1) When using a separate heat sink,
you must use a heat sink that meets the thermal resistance table.
Surge current Characteristics
10A ~ 40A
Input
current
(mA)
Input voltage(V)
Input voltage(V)
Input
current
(mA)
Load
current
(A)
Ambient temperature(℃)
HSR-2□40
HSR-2□30
HSR-2□10
80
70
60
HSR-2□70
HSR-2□50
Surge
current
(A)
Number of cycle(60Hz)
0
50
100
150
200
250
300
350
400
450
500
550
600
1
10
100
100C
HSR-2□70
HSR-2□50
Surge
current
(A)
Number of cycle(60Hz)
HSR-2□40
HSR-2□30
HSR-2□20/25
HSR-2□10
HSR-2□20
50A ~ 70A
Input
current
(mA)
Input voltage(V)
Input voltage(V)
Input
current
(mA)
Load
current
(A)
Ambient temperature(℃)
HSR-2□40
HSR-2□30
HSR-2□10
80
70
60
HSR-2□70
HSR-2□50
Surge
current
(A)
Number of cycle(60Hz)
0
50
100
150
200
250
300
350
400
450
500
550
600
1
10
100
100C
HSR-2□70
HSR-2□50
HSR-2□55
Surge
current
(A)
Number of cycle(60Hz)
HSR-2□40
HSR-2□30
HSR-2□20
HSR-2□10
HSR-2□20
ㆢ㈵ㆤ
ㆤㆨ
ㇵㆥ
ㆢ㈵ㆤ
ㆤㆨ
ㇵㆥ
※ CAUTION 1 (thermal resistance table)
• Input terminal wiring
• Output terminal wiring
1 X 0.5 mm² (1 X AWG20) or larger
1 X 1.5mm² (1 X AWG16) or larger
1 X 1.5 mm² (1 X AWG16) or less than 2 X 1.5 mm² (2 X AWG16) 1 X 16 mm² (1 X AWG6) or less than 2 X 6 mm² (2 X AWG10)
※ Connect the wiring suitable for the load current capacity
to the output terminal.
Model
Applicable Model
Capacity (A)
Length(L)
Weight
HSM-70
HSR-2□10□
10A
70 mm
352 (g)
HSM-110
HSR-2□20□
20A
110 mm
558 (g)
HSM-150
HSR-2□30□
HSR-2□40□
30A
40A
150 mm
758 (g)
HSN-80
HSR-2□50□
50A
80 mm
1,146 (g)
HSN-120
HSR-2□70□
70A
120 mm
1,712 (g)
load capacity
Heatsink thermal resistance (40℃ standard)
10A
2.00 ℃/W
20A
1.00 ℃/W
30A
0.50 ℃/W
40A
0.25 ℃/W
50A
0.30 ℃/W
70A
0.15 ℃/W
25 ℃ 10A 20A 30A 40A 50A 55A 70A
80 ℃ 6A
8A 15A 15A 15A 15A 16A