background image

BISTABLE RELAY PBM-07 

MANUAL INSTRUCTION

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

PBM-07_inst_ext_GB | 05.05.21

APPEARANCE

FEATURES

DESCRIPTION

● control of lighting and other devices 

according to a defined sequence,

● output status indicated by red LEDs 

(2 x red LED),

● power supply indication (1 x green LED),

● system release only from the “L” line,

● possibility of cooperation with unipolar 

backlit push buttons,

● two-wire control installation,

● two independent relay outputs – (dry 

contacts) 2 NO /NC contacts with a ma-

ximum load of 16 A,

● mounting in distribution boards 

  (TH35 rail).

The PBM-07 bistable relay is used to con-

trol lighting or any other device by means 

of  unipolar  push  buttons  connected  in 

a parallel way. The relay is equipped with 

two outputs activated by means of impuls-

es given to the (IN) input. It allows to con-

trol two circuits / branches simultaneously. 

The  control  impulse  must  be  the  “L”  line 

signal. The trigger input structure enables 

cooperation with backlit push buttons (in-

cluding  LED  backlight).  The  total  current 

of backlight for the (IN) input can not ex-

ceed 1,5 mA. The device is designed to be 

mounted in distribution boards (TH35 rail). 

LEDs  on  the  front  panel  indicate  power 

supply (green LED) and the output status 

(2 x red LED).

TECHNICAL DATA

Input (supply) terminals: L, N

Nominal supply voltage: 230 V AC

Nominal supply voltage tolerance: -15 ÷ +10 %

Nominal frequency: 50 Hz

Nominal power consumption:  stand-by: 0,4 W

2 active outputs: 1,1 W

Optical signalling of relay status: 2x red LED

Release terminals:  IN, IN

Release control current: 7,5 mA

Cooperation with backlit push buttons: yes

Total current of the push button backlight:  < 1,5 mA

Minimum impulse release time:  70 ms

Output devices: 2 x relays

Relay contact parameters: NO/NC – 16 A / 250 VAC

Number of connection terminals: 10

Cross-section of connection cables:  0,2 ÷ 2,5 mm

2

Operating temperature range: -20 ÷ +45 

o

C

Operating position: free

Casing mounting:  TH35 rail

Casing protection degree: IP20

Overvoltage category: II

Pollution degree: 2

Dimensions: 90 x 17,5 x 66 mm

Weight:  0,090 kg

Connect  this  product  to  a 

single-phase  power  system  ac-

cording  to  applicable  electrical 

and  safety  standards  and  regu-

lations.  See  this  Manual  for  the 

wiring  instructions.  Installation, 

wiring  and  adjustment/setting  shall  only  be 

done by qualified electricians who have read 

and  understood  this  User  Manual  and  the 

functions of the product. Do not open or oth-

erwise disassemble the product housing; oth-

erwise the product warranty will be void and 

an  electrocution  hazard  may  occur.  Prior  to 

installing  and  wiring  this  product,  make  sure 

that the wiring to be connected is not live. The 

conditions and methods of transport, storage 

and  operation  of  this  product  may  affect  its 

performance. Do not install the product if any 

of its components are missing, the product is 

damaged or deformed in any way. If any mal-

functions are found, consult the manufacturer.

CAUTION

Do not dispose of this device with other 

waste! In order to avoid harmful effects on 

the environment and human health, the 

used device should be stored in designated 

areas. For this purpose, you can dispose 

of household waste free of charge and in 

any quantity to a collection point set up, 

as well as to the shop when you buy new 

equipment.

Input (supply) terminal (L)

PK1 (11,14,12) output relay 

terminals

PK2 (21,24,22) output relay 

terminals

Input (supply) terminal (N)

Release terminals (IN)

Power supply indicator
PK1 status indicator
PK2 status indicator

Отзывы: