CZ3055

               Isolator

   

The

 

frequency

 

transducer

frequency

 

signal

 

will

 

be

 

set

 

according

 

to

 

the

 

user

 

to

 

convert

 

the

 

linear

 

range

 

4

~

20mA

  (

or

 

0

~

20mA

)

output

.

The

 

product

 

has

 

one

 

relay

 

alarm

 

output

.

This

 

product

 

need

 

be

 

supplied

 

independently

,

and

 

the

 

power

 

supply

,

input

 

and

 

output

 

are

 

isolated

 

from

 

each

 

other

.  

1

2

Number

 

of

 

channels: 1

Supply

 

voltag: 20

~

35V DC

Current

 

consumption: (24V

 

power supply,20mA

 

output

 

Relay closure

)

90mA

Input: 

   

Signal type:

           1) 3-wire

 

PNP/NPN

 

sensor

 

output:

         

Sensor

 

distribution: 14V

 

DC,  current: 

<

20mA

         

Input

 

frequency: 0.1Hz

~

100kHz

      

2) Frequency

 

input

 

signal: 

         

Input

 

frequency: 0

.

1Hz

~

100kHz

         

Maximum

 

input

 

voltage: 30Vp-p

         

Minimum

 

input

 

level: 

   

2V, (2Hz

~

100KHz)

           

2V, (0.1Hz

~

100KHz)

     

3) Proximity

 

switch, dry

 

contact

 

switch

 

input:

         

Sensor distribution: approx

8V; short-circuit

 

current: approx

8mA

     

                Input

 

frequency: 0.1Hz

~

100kHz

Output:

      Current: 0

~

20mA/4

~

20mA

           

Load

 

resistance: 

400

Ω

   

Voltage: 0

~

5V/1

~

5V

           

Load

 

resistance: 

300k

Ω

                         

Transfer

 

accuracy: 0

.

1

F

.

S

.

Temperature

 

drift: 0.01

%

F

.

S

./℃

Relay

 

characteristics:

   

Response

 

time: 

20ms

   

Drive

 

ability: 250V

 

AC/2A

 

or

 

30V

 

DC/2A

   

Load

 

type: Resistive

 

load

Pulse

 

width: 

2

μ

s

Input

 

signal

 

fault

 

detection

 

function:

        If  the  input  signal  exceeds  the  top  measuring  range  set,output  current  22mA(or 
output voltage 5.5V), the relay aets as the input, SPH LED ON, faceplate display “full”.
        If  the  input  signal  fallen  below  the  measuring  range  set,  output  current  3mA  (or 
output  voltage  0.75V),  the  relay  aets  as  the  input,  SPL  LED  ON,  faceplate  display 
“nfull”.
        If  the  input  signal  fault  and  input  signal  can’t  transmission,output  current2mA(or 
output voltage 0.5V),the relay aets as the input, SPH.SPL ON,faceplate display “no in”.
input signal model is: in2.H/in2.r: 
     If the input loop-current I

<

0.1mA, proximity switch alarm(break line), output current 

2mA,the relay aets as the input,SPH.SPL LED ON, faceplate display “inopn”.     
     If the input loop-current I

6mA, proximity switch alarm(shout circuit)output current 

2mA, the relay aets as the input, SPH.SPL  LED ON, faceplate display “insot”.
          Note:  If  input  signal  top  limit  overflows  or  lower  limit  overflows  or  input  signal 
faults,  the  output  current  can  be  configured  to  any  value  of  0~24mA  (0~6V  for 
voltage) separately.
Start delay time: 0~9999s

   

When the output relay is set to alarm

 

mode

 

with

 

under-speed, the

 

instrument

 

will not output an alarm signal during the launch delay time after power on due to the

 

under speed of input signal

.

Input

 

fault

 

response

 

time: 0.1~999.9s

The input signal pattern choice:

   

in  H:Frequency  input  for  NAMUR(2

3

4-wire  sensor,  dry  contact 

switch,incremental encoders)at Hz.

   

in  r:  Frequency  input  for  NAMUR(2

3

4-wire  sensor,  dry  contact 

-1

switch,ncremental encoders) at min .

   

in2  H:  Switching  input  for  NAMUR,with  input  wirebreak  and  input  short-circuit 

recognition. at Hz.

   

in2 r: Switching input for NAMUR,switching input for NAMUR,with input wirebreak 

-1

and input short-circuit recognition.at min .

-1

     Not: If users need to switch measurement display unit, (Hz or min ), you need to  
set measuring range

alarm

alarm hystersis and so on.

The LED indicator light instructions:

   

SPH: If the input signal exceeds the top alarm(contains dead band) LED ON.

   

SPL: If input signal fallen below the alarm(contains dead band) LED ON.

   

SPH

SPL ON: Input signal fault.

      RAL ON: Output relay closure.

User

 

Manual

YEAR

YEAR

WARRANTY

WARRANTY

    Please read the instruction manual carefully before use the product, 
and please safekeeping.

Caution

Please check whether the product type on the package accords

to the ordering contract;

Read this manual carefully before installation or using. If there is 

something unclear,please dial technic support hotline-400 881 0780;

Supply voltage is 24VDC, 220VAC is forbidden;

Users are not allowed to dismantle or repair the Isolator otherwise 

it will induce malfunction.

Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park 
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350   Fax : +86-21-64846984
Email

chenzhu

@

chenzhu

-

inst

.

com

http://www.chenzhu-inst.com

Summarize

Specification

CZ.CZ3055.11(S)E-5.0/17.11

Отзывы: