background image

Installation Sheet

RDM-ZC Zero Cross Module

2400 W

The RDM-ZC Zero Cross Module is a 2400 W zero-cross relay built for long 
term, reliable switching of electronic fluorescent ballasts, electronic trans-
formers and incandescent lamps. It is designed for use with the RDA series 
of enclosures, in an AMX Lighting™ modular digital dimming system. The 
RDM-ZC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL 
approved.  

RDM-ZC UL and C-UL Ratings

120-277 VAC, 50/60 Hz, 2400 W

240/277 VAC, 50/60 Hz, 2400 W

Suggested Switched Loads

Incandescent

Electronic transformers

HID ballast

Electronic and magnetic ballast

Specifications

Dimensions (HW):  10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size:  10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight:  1.5 lbs. (0.68 kg)

BTU/hr: 150

Control current: 45 mA @ 12 VDC

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

This module may require extra power from the AXlink connection or an 

external power supply connected to the control card.

Connecting the RDM-ZC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1  RDM-ZC

Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller

Zero cross 

Line in (hot)
Load out

High-voltage
connections

Mounting points

relay

FIG. 2  RDM-ZC connections

FIG. 3  RDM-ZC wiring configuration

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-ZC 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).

 

Circuit breaker
panel

 

Neon lights

(cold-cathode, on/off)

Neutral

Load

All neutrals are common
to the Neutral block in the
enclosure. Provide a 
separate neutral for 
each load.

Load

Line in (HOT)

Neutral

 

 

BALLAST

 

BALLAST

 

Load

Neutral

Fluorescent Ballast

Zone 1

Incandescent track

lighting

Отзывы: