The beginning of the cooling process deactivates the
TRIP
output and activates the
COOL_ACTIVE
output.
COOL_ACTIVE
is kept active during the cooling process. If a
new overexcitation start ceases cooling,
COOL_ACTIVE
is deactivated during that start
time.
BLK_RESTART
is kept active until the set total cooling time has elapsed. It means
that even during the new overexcitation start ceases cooling,
BLK_RESTART
is kept
active. Due to the updated cooling time, the
BLK_RESTART
activation time is prolonged
with these new starts during cooling. A new overexcitation start during cooling does not
immediately reactivate
TRIP
, but
PICKUP
is first activated and a new
TRIP
activation
depends on the already run cooling time. If, for example, 60 percent of the set cooling time
has run before a new start, 40 percent of the operating time is needed to reactivate
TRIP
.
The
T_ENARESTART
output indicates in seconds the duration for which the
BLK_RESTART
output still remains active. The value is available in the Monitored data
view.
Timer calculates the pickup duration value PICKUP_DUR, which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available in the
Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration/System/Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block TRIP output" mode, the function
operates normally but the
TRIP
output is not activated.
4.2.5.5
Timer characteristics
24 supports both DT and IDMT characteristics. The DT timer characteristics can be
selected as "ANSI Def. Time" or "IEC Def. Time" in the
Operating curve type
setting. The
functionality is identical in both cases. When the DT characteristics are selected, the
functionality is only affected by the
Trip delay time
and
Reset delay time
settings.
24 also supports four overexcitation IDMT characteristic curves: "OvExt IDMT Crv1",
"OvExt IDMT Crv2", "OvExt IDMT Crv3" and "OvExt IDMT Crv4".
Section 4
1MRS240050-IB C
Protection functions
250
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...