GUID-7B0FC64E-8C0B-4742-8252-522B91EFC4BC-ANSI V1 EN
Figure 106:
Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the
Pickup value
setting. The
Operation mode
setting can be used to select the "Three Phase" or "Single Phase" mode.
If in the "Three Phase" mode all the phase current values are less than the value of the
Pickup value
setting, the condition is detected and an enabling signal is sent to the timer.
This signal is disabled after one or several phase currents have exceeded the set
Pickup
value
value of the element.
If in the "Single Phase" mode any of the phase current values are less than the value of the
Pickup value
setting, the condition is detected and an enabling signal is sent to the timer.
This signal is disabled after all the phase currents have exceeded the set
Pickup value
value
of the element.
The protection relay does not accept the
Pickup value
to be smaller than
Current block value
.
Level detector 2
This is a low-current detection module that monitors the de-energized condition of the
protected object. The module compares the phase currents (RMS value) to the
Current
block value
setting. If all the phase current values are less than the
Current block value
setting, a signal is sent to block the operation of the timer.
Timer
Once activated, the timer activates the
PICKUP
output and the phase-specific
PICKUP_X
output. The time characteristic is according to DT. When the operation timer has reached
the value set by
Trip delay time
, the
TRIP
output and the phase-specific
TRIP_X
output
are activated. If the fault disappears before the module trips, the reset timer is activated.
1MRS240050-IB C
Section 4
Protection functions
REF615R
219
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...