GUID-0ADB8235-8AF9-45D6-B790-5C710DCE66CF V1 EN
Figure 266:
Status indication-based interlocking via the GOOSE messaging
The vector group of the power transformer is defined with clock numbers, where the value
of the hour pointer defines the low-voltage-side phasor and the high-voltage-side phasor
is always fixed to the clock number 12, which is same as zero. The angle between clock
numbers is 30 degrees. When comparing phase angles, the
V_BUS
input is always the
reference. This means that when the Yd11 power transformer is used, the low-voltage-
side voltage phasor leads by 30 degrees or lags by 330 degrees the high-voltage-side
phasor. The rotation of the phasors is counterclockwise.
The generic rule is that a low-voltage-side phasor lags the high-voltage-side phasor by
clock number * 30º. This is called angle difference adjustment and can be set for 25 with
the
Phase shift
setting.
9.3.5
Application
The main purpose of the synchrocheck function is to provide control over the closing of
the circuit breakers in power networks to prevent the closing if the conditions for
1MRS240050-IB C
Section 9
Control functions
REF615R
505
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...