CCM
I_A
I_B
ALARM
FAIL
I_C
I_REF
BLOCK
protection relay
Core 1
(p
ro
tectio
n)
IL1
IL2
IL3
I_A
I_B
I_C
I_REF
Other protection devices
Co
re 2
(p
rot
ection)
GUID-8DC3B17A-13FE-4E38-85C6-A228BC03206B-ANSI V3 EN
Figure 193:
Connection diagram for current circuit supervision with two sets of three-
phase current transformer protection cores
When using the measurement core for reference current measurement, it
should be noted that the saturation level of the measurement core is much
lower than with the protection core. This should be taken into account
when setting the current circuit supervision function.
1MRS240050-IB C
Section 6
Supervision functions
REF615R
367
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...