If more than one CBBs are started with the shot pointer, the CBB with the
smallest individual number is always selected. For example, if the
INIT_2
and
INIT_4
lines are active for the second shot, that is, the shot
pointer is 2, CBB2 is started instead of CBB5.
Even if the initiation signals are not received from the protection functions, the AR
function can be set to continue from the second to the fifth reclose shot. The AR function
can, for example, be requested to automatically continue with the sequence when the
circuit breaker fails to close when requested. In such a case, the AR function issues a
CLOSE_CB
command. When the wait close time elapses, that is, the closing of the circuit
breaker fails, the next shot is automatically started. Another example is the embedded
generation on the power line, which can make the synchronism check fail and prevent the
reclosing. If the autoreclose sequence is continued to the second shot, a successful
synchronous reclosing is more likely than with the first shot, since the second shot lasts
longer than the first one.
The existing 79 function does not have a complete zone sequence coordination feature. An
external ACT logic needs to be built to drive INC_POINT.
Section 9
1MRS240050-IB C
Control functions
480
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...