4.1.7.8
Monitored data
Table 157:
46 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
46
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.1.7.9
Technical data
Table 158:
46 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current:
f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Pickup time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2 × set
Pickup value
I
Fault
= 10 × set
Pickup value
22 ms
14 ms
25 ms
17 ms
27 ms
19 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Negative sequence current before fault = 0.0, f
n
= 60 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 1.5...20
4.1.8
Phase discontinuity protection 46PD
4.1.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase discontinuity protection
PDNSPTOC
I2/I1>
46PD
Section 4
1MRS240050-IB C
Protection functions
212
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...