It is possible to block the
SPR_CHR_ALM
alarm signal by activating the
BLOCK
binary
input.
6.1.4.8
Gas pressure supervision
The gas pressure supervision subfunction monitors the gas pressure inside the arc
chamber.
The operation of the subfunction can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
A071113 V2 EN
Figure 187:
Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals
PRES_LO_IN
and
PRES_ALM_IN
.
Timer 1
When the
PRES_ALM_IN
binary input is activated, the
PRES_ALM
alarm is activated
after a time delay set with the
Pressure alarm time
setting. The
PRES_ALM
alarm can be
blocked by activating the
BLOCK
input.
Timer 2
If the pressure drops further to a very low level, the
PRES_LO_IN
binary input becomes
high, activating the lockout alarm
PRES_LO
after a time delay set with the
Pres lockout
time
setting. The
PRES_LO
alarm can be blocked by activating the
BLOCK
input.
6.1.5
Application
52CM includes different metering and monitoring subfunctions.
Circuit breaker status
Circuit breaker status monitors the position of the circuit breaker, that is, whether the
breaker is in an open, closed or intermediate position.
1MRS240050-IB C
Section 6
Supervision functions
REF615R
355
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...