Negative sequence voltage as polarizing quantity
When the negative voltage is used as the polarizing quantity, the angle difference between
the operating and polarizing quantity is calculated with the same formula for all fault
types:
ANGLE
X
V
I
RCA
_
(
)
(
)
=
−
−
−
ϕ
ϕ
ϕ
2
2
GUID-7AC132D5-033D-468F-ADB6-7E04C3C7E153-ANSI V1 EN
(Equation 1)
This means that the actuating polarizing quantity is -V2.
GUID-41DF2169-686B-4564-98D5-B09F7F6BBEA0-ANSI V1 EN
Figure 72:
Phasors in a single-phase ground fault, phases A-N, and two-phase short
circuit, phases B and C, when the actuating polarizing quantity is the
negative-sequence voltage -V2
Positive sequence voltage as polarizing quantity
Table 101:
Equations for calculating angle difference for positive-sequence quantity polarizing method
Faulted
phases
Used fault
current
Used
polarizing
voltage
Angle difference
A
I
A
V1
ANGLE
A
V
I
A
RCA
_
(
)
(
)
=
−
−
ϕ
ϕ
ϕ
1
GUID-7BCB8B12-2484-49AD-92A3-839A39BE5D01-ANSI V1 EN
B
I
B
V1
ANGLE
B
V
I
B
RCA
_
(
)
(
)
=
−
−
−
ϕ
ϕ
ϕ
1
120
o
GUID-E4D7718C-A73E-46C6-89A6-8EEFDBEAB046-ANSI V1 EN
C
I
C
V1
ANGLE
C
V
I
C
RCA
_
(
)
(
)
=
−
−
+
ϕ
ϕ
ϕ
1
120
o
GUID-6BCAA5DE-778A-4623-B196-2433045A5B2A-ANSI V1 EN
Table continues on next page
1MRS240050-IB C
Section 4
Protection functions
REF615R
149
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...