The retrip logic is inactive if the
CB fail retrip mode
setting is set to "Disabled".
•
If
CB fail retrip mode
is set to the "Current check" mode, the activation of the retrip
output
TRRET
depends on the
CB failure mode
setting.
•
If
CB failure mode
is set to the "Current" mode,
TRRET
is activated when the
value of any phase current exceeds the
Current value
setting. The
TRRET
output remains active for the time set with the
Trip pulse time
setting or until all
phase current values drop below the
Current value
setting, whichever is longer.
•
If
CB failure mode
is set to the "Breaker status" mode,
TRRET
is activated if the
circuit breaker is in the closed position. The
TRRET
output remains active for
the time set with the
Trip pulse time
setting or the time the circuit breaker is in
the closed position, whichever is longer.
•
If
CB failure mode
is set to "Both",
TRRET
is activated when either of the
"Breaker status" or "Current" mode condition is satisfied.
•
If
CB fail retrip mode
is set to the "Without check" mode,
TRRET
is activated once
the timer 1 is activated without checking the current level. The
TRRET
output
remains active for a fixed time set with the
Trip pulse time
setting.
The activation of the
BLOCK
input or the
CB_FAULT_AL
output deactivates the
TRRET
output.
POSCLOSE
50P
From Level detector 1
Timer 1 elapsed
From Timer 1
OR
AND
AND
CB fail retrip mode
”Without check”
CB fail retrip mode
”Current check”
CB failure mode ”Current”
CB failure mode ”Breaker
status”
CB failure mode ”Both”
AND
AND
AND
OR
OR
AND
TRRET
BLOCK
CB_FAULT_AL
From Timer 3
GUID-BD64DEDB-758C-4F53-8287-336E43C750F2-ANSI V2 EN
Figure 158:
Retrip logic
Backup trip logic
The backup trip logic provides the
TRBU
output which can be used to trip the upstream
backup circuit breaker when the main circuit breaker fails to clear the fault. The backup
trip logic is activated by the timer 2 module or timer-enabling signal from the start logic
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
323
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...