A071109 V2 EN
Figure 183:
Functional module diagram for calculating accumulative energy and
alarm
Accumulated energy calculator
This module calculates the accumulated energy I
y
t [(kA)
y
s]. The factor y is set with the
Current exponent
setting.
The calculation is initiated with the
POSCLOSE
input opening events. It ends when the
RMS current becomes lower than the
Acc stop current
setting value.
A071110 V1 EN
Figure 184:
Significance of the Difference Cor time setting
The
Difference Cor time
setting is used instead of the auxiliary contact to accumulate the
energy from the time the main contact opens. If the setting is positive, the calculation of
energy starts after the auxiliary contact has opened and when the delay is equal to the value
set with the
Difference Cor time
setting. When the setting is negative, the calculation starts
in advance by the correction time before the auxiliary contact opens.
The accumulated energy outputs
IPOW_A (_B, _C)
are available in the monitored
data view on the LHMI or through tools via communications. The values can be reset by
setting the parameter
Initial CB Rmn life
setting to true in the clear menu from WHMI or
LHMI.
Section 6
1MRS240050-IB C
Supervision functions
352
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...